Mitsubishi Electronics FX5U Coffeemaker User Manual


 
84
6 WIRING
6.5 Input Wiring
Handling of 24 V DC input
Input terminal
Input circuit
Input sensitivity
Sink input Source input
When a no-voltage contact or NPN open collector transistor output
is connected between an input (X) terminal and the [0V] terminal
and the circuit is closed, the input (X) turns on.
The input display LED turns on.
When a no-voltage contact or PNP open collector transistor output
is connected between an input (X) terminal and the [24V] terminal
and the circuit is closed, the input (X) turns on.
The input display LED turns on.
RUN terminal setting
X000 to X017 of the CPU module can be used as RUN input terminals
by setting parameters.
MELSEC iQ-F FX5 User's Manual (Application)
Function of input circuit
The primary and secondary circuits for input are insulated with a photocoupler, and the second circuit is provided with a C-R filter.
The C-R filter is designed to prevent malfunctions caused by chattering of the input contact and noise from the input line.
Input has a response delay switching from ON to OFF and OFF to ON, shown in the following table.
Item Specifications
Input response time
(H/W filter delay)
FX5U-32M X000 to X005 ON: 2.5 s or less
OFF: 2.5 s or less
FX5U-64M,
FX5U-80M
X000 to X007
FX5U-32M X006 to X017 ON: 30 s or less
OFF: 50 s or less
FX5U-64M,
FX5U-80M
X010 to X017
FX5U-64M,
FX5U-80M
X020 and
subsequent
ON: 50 s or less
OFF: 150 s or less
I/O module
Change of filter time
All input circuits have digital filters, and the input response time shown in the following table can be added by setting parameters.
When using this product in an environment with much noise, set the digital filter.
Item Specifications
Input response time
(Digital filter setting value)
None, 10 s, 50 s, 0.1 ms, 0.2 ms, 0.4 ms, 0.6 ms, 1 ms, 5 ms, 10 ms (initial values), 20 ms, 70 ms
For input signal current and Input sensitivity current of the CPU module, refer to Page 19 Input Specifications.
For input signal current and Input sensitivity current of the I/O modules, refer to Page 135 Input specifications.
X000
X001
X007
*
*Input impedance
S/S
N
L
100 to 240 V AC
Fuse
24V
0V
X000
X001
X007
*
*Input impedance
S/S
N
L
100 to 240 V AC
Fuse
24V
0V