(7) Pr. 363 "in-position signal output delay time".
When the motor shaft enters the in-position zone, the in-position signal is output after a delay of the time set in
Pr. 363. Also, when the motor shaft comes out of the in-position zone, the in-position signal is switched off after a
delay of the time set in Pr. 363.
(8) Pr. 364 "PLG stop check time".
When the in-position signal has not yet been output in orientation operation, the orientation fault signal is output if
orientation cannot be completed and the PLG is stopped for the period of time set in Pr. 364. When the in-
position signal has been output once, the orientation fault signal is output if the orientation cannot be completed
again within the time set in Pr. 364.
(9) Pr. 365 "orientation time limit".
If orientation cannot be completed within the time set in Pr. 365, which is measured from when the current
position signal has passed the creep select position, the orientation fault signal is output.
(10) Pr. 366 "recheck time".
If the start signal is switched off with the orientation command ON after the PLG is stopped under orientation
control, the current position is checked again after the time set in Pr. 366 has elapsed and the in-position signal
or orientation fault signal is output according to the check result.