Mitsubishi FR-A5AP Oven User Manual


 
52
(3) Pr. 374 "overspeed detection level".
Used to limit the maximum speed. (0 to 400Hz)
Any speed higher than the speed set in Pr. 374 is judged as overspeed and the corresponding signal is output.
If overspeed is detected, the inverter will not come to an alarm stop.
Speed
(
r/min
)
OFF ON
Pr.374
Speed set in Pr. 374
Overspeed detection
output
(
Y29
)
(
Note
)
Time
Note: Assign the function to any of the terminals using Pr. 190 to Pr. 195 "output terminal function selection".
(4) Forward/reverse running signal output.
Whether forward or reverse rotation is being made is output as a signal according to the actual speed.
Assign the function of the output signal to any of the terminals using Pr. 190 to Pr. 195 "output terminal function
selection".