RLC-PRC006-EN20
Table P-1 — 60 Hz Standard Efficiency Machines in English Units
Condenser Entering Air Temperature (F)
85 95 105 115
Evaporator
Leaving Water Unit Size
Temperature (F) Model RTAC Tons kW input EER Tons kW input EER Ton kW input EER Tons kW input EER
140 STD 140.5 139.8 10.9 131.1 152.4 9.4 121.2 166.6 8.0 111.1 182.5 6.7
155 STD 154.4 152.3 11.0 144.2 166.0 9.5 133.6 181.5 8.1 122.7 198.8 6.8
170 STD 168.5 164.8 11.0 157.5 179.7 9.5 146.1 196.5 8.2 134.5 215.2 6.9
185 STD 184.1 183.7 10.8 172.2 199.9 9.4 159.8 218.1 8.0 147.1 238.5 6.8
200 STD 199.8 202.7 10.7 186.9 220.1 9.3 173.5 239.9 7.9 159.6 262.0 6.7
40 225 STD 220.2 222.6 10.7 206.2 241.6 9.3 191.6 263.2 8.0 176.4 287.4 6.8
250 STD 241.1 242.8 10.8 225.9 263.4 9.4 209.9 286.9 8.1 193.4 313.1 6.8
275 STD 267.0 266.8 10.8 250.0 290.4 9.4 232.3 317.0 8.0 213.9 346.7 6.8
300 STD 301.3 320.6 10.6 281.1 348.3 9.2 260.2 379.5 7.8 235.9 408.7 6.6
350 STD 338.7 346.9 10.6 317.5 376.0 9.2 295.3 409.1 7.9 272.2 446.3 6.8
400 STD 400.2 408.4 10.6 374.6 442.8 9.2 347.9 481.9 7.9 320.1 525.8 6.7
450 STD 436.7 449.3 10.6 409.1 487.0 9.2 380.3 529.7 8.0 350.3 577.7 6.8
500 STD 477.2 490.6 10.6 447.3 531.3 9.3 416.0 577.7 8.0 383.4 629.6 6.8
140 STD 145.6 142.7 11.1 135.9 155.4 9.6 125.8 169.7 8.2 115.3 185.7 6.9
155 STD 160.0 155.4 11.1 149.5 169.3 9.6 138.6 184.9 8.2 127.4 202.2 7.0
170 STD 174.6 168.2 11.2 163.3 183.2 9.7 151.6 200.1 8.3 139.6 218.9 7.0
185 STD 190.7 187.6 11.0 178.4 203.9 9.5 165.7 222.3 8.2 152.5 242.8 7.0
200 STD 206.8 207.1 10.8 193.6 224.6 9.4 179.8 244.5 8.1 165.5 266.8 6.9
42 225 STD 228.0 227.6 10.9 213.6 246.8 9.5 198.5 268.5 8.1 182.8 292.9 6.9
250 STD 249.7 248.4 10.9 234.0 269.3 9.5 217.5 292.9 8.2 200.4 319.3 7.0
275 STD 276.5 272.4 11.0 259.0 296.1 9.5 240.8 322.9 8.2 221.9 352.8 7.0
300 STD 311.5 327.8 10.8 290.7 355.8 9.3 269.2 387.2 7.9 237.7 402.9 6.8
350 STD 350.7 354.8 10.7 328.8 384.2 9.4 305.9 417.5 8.1 282.0 454.9 6.9
400 STD 414.3 417.3 10.8 388.0 452.0 9.4 360.5 491.4 8.1 331.9 535.5 6.9
450 STD 452.2 459.5 10.8 423.7 497.5 9.4 394.0 540.6 8.1 363.1 588.9 6.9
500 STD 494.2 502.1 10.8 463.3 543.2 9.4 431.0 589.9 8.1 397.2 642.2 6.9
140 STD 150.8 145.7 11.3 140.8 158.5 9.7 130.4 172.9 8.3 119.6 188.9 7.0
155 STD 165.7 158.6 11.3 154.8 172.6 9.8 143.7 188.3 8.4 132.1 205.7 7.1
170 STD 180.8 171.7 11.4 169.1 186.8 9.9 157.1 203.8 8.5 144.8 222.6 7.2
185 STD 197.4 191.6 11.2 184.7 208.0 9.7 171.6 226.5 8.3 158.1 247.1 7.1
200 STD 214.0 211.6 11.0 200.4 229.2 9.6 186.1 249.3 8.2 171.4 271.7 7.0
44 225 STD 236.0 232.7 11.0 221.1 252.0 9.6 205.5 273.9 8.3 189.3 298.4 7.0
250 STD 258.4 254.2 11.1 242.2 275.2 9.6 225.2 299.0 8.3 207.4 325.6 7.1
275 STD 286.1 278.0 11.2 268.1 302.0 9.7 249.4 328.9 8.3 230.0 359.0 7.1
300 STD 321.8 335.2 10.9 300.4 363.4 9.6 278.2 395.1 8.1 239.3 396.1 6.9
350 STD 362.8 362.8 10.9 340.2 392.5 9.6 316.6 426.1 8.2 291.9 463.7 7.0
400 STD 428.7 426.4 10.9 401.5 461.3 9.6 373.2 501.0 8.2 343.8 545.5 7.0
450 STD 467.9 469.9 10.9 438.5 508.2 9.6 407.9 551.6 8.2 375.9 600.2 7.0
500 STD 511.5 513.8 10.9 479.5 555.3 9.6 446.1 602.4 8.2 411.2 655.0 7.0
Notes:
1. Ratings based on sea level altitude and evaporator fouling factor of 0.00010.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kW input is for compressors only.
4. EER = Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 10°F.
6. Ambient temperatures 115° F and greater reflect the high ambient condenser option.
7. Interpolation between points is permissible. Extrapolation is not permitted.
8. Rated in accordance with ARI Standard 550/590-98.
Performance
Data
Full Load