Trane RLC-PRC006-EN Beverage Dispenser User Manual


 
37RLC-PRC006-EN
Electrical
Data
Table E-1 (Continued) Unit Electrical Data for Std Efficiency at All Ambient Operation
Unit Wiring Motor Data
# of Max. Fuse, HACR Rec. Time Compressor (Each) Fans (Each)
Unit Rated Power MCA (3) Breaker or MOP (11) Delay or RDE (4) RLA (5) XLRA (8) YLRA (8) Qty. Control
Size Voltage Conns (1) Ckt 1/Ckt 2 Ckt 1/Ckt 2 Ckt 1/Ckt 2 Qty Ckt 1/Ckt 2 Ckt 1/Ckt 2 Ckt 1/Ckt 2 Ckt 1/Ckt 2 kW FLA kW (7)
200/60/3 1 NA
200/60/3 2 1124/947 1200/1200 1200/1200 4 459-459/386-386 NA 821-821/701-701 14/12 1.5 6.5 1.59
230/60/3 1 NA
230/60/3 2 989/834 1200/1000 1200/1000 4 399-399/336-336 NA 691-691/571-571 14/12 1.5 6.5 1.59
RTAC 380/60/3 1 NA
450 380/60/3 2 594/499 800/700 700/600 4 242-242/203-203 1306-1306/1060-1060 424-424/345-345 14/12 1.5 3.5 1.59
460/60/3 1 864 1000 1000 4 200-200-168-168 1065-1065-878-878 346-346-285-285 26 1.5 3.0 1.59
460/60/3 2 492/414 600/500 600/500 4 200-200/168-168 1065-1065/878-878 346-346/285-285 14/12 1.5 3.0 1.59
575/60/3 1 693 800 800 4 160-160-134-134 853-853-705-705 277-277-229-229 26 1.5 2.5 1.59
575/60/3 2 395/332 500/450 450/400 4 160-160/134-134 853-853/705-705 277-277/229-229 14/12 1.5 2.5 1.59
200/60/3 1 NA
200/60/3 2 1124/1124 1200/1200 1200/1200 4 459-459/459-459 NA 821-821/821-821 14/14 1.5 6.5 1.59
230/60/3 1 NA
230/60/3 2 989/989 1200/1200 1200/1200 4 399-399/399-399 NA 691-691/691-691 14/14 1.5 6.5 1.59
RTAC 380/60/3 1 NA
500 380/60/3 2 594/594 800/800 700/700 4 242-242/242-242 1306-1306/1306-1306 424-424/424-424 14/14 1.5 3.5 1.59
460/60/3 1 934 1000 1000 4 200-200-200-200 1065-1065-1065-1065 346-346-346-346 28 1.5 3.0 1.59
460/60/3 2 492/492 600/600 600/600 4 200-200/200-200 1065-1065/1065-1065 346-346/346-346 14/14 1.5 3.0 1.59
575/60/3 1 750 800 800 4 160-160-160-160 853-853-853-853 277-277-277-277 28 1.5 2.5 1.59
575/60/3 2 395/395 500/500 450/450 4 160-160/160-160 853-853/853-853 277-277/277-277 14/14 1.5 2.5 1.59
Notes:
1. As standard, 140-250 ton (60 Hz) units and 140-200 ton (50 Hz) units have single point power connections. Optional dual point power connections are available. As standard,
275-500 ton (60 Hz) units and 250-400 ton (50 Hz) units have dual point power connections. Optional single point power connections are available on 380V, 460V, 575 V/60 Hz and
400V/50 Hz units.
2. Max Fuse or HACR type breaker = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA, plus the sum of the condenser fan FLA per NEC 440-22.
Use FLA per circuit, NOT FLA for the entire unit).
3. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of the second compressor RLA plus the sum of the condenser fans FLAs per NEC 440-33.
4. RECOMMENDED TIME DELAY OR DUAL ELEMENT (RDE) FUSE SIZE: 150 percent of the largest compressor RLA plus 100 percent of the second compressor RLA and the sum of the condenser
fan FLAs.
5. RLA - Rated Load Amps - rated in accordance with UL Standard 1995.
6. Local codes may take precedence.
7. Control kW includes operational controls only. Does not include evaporator heaters.
8. XLRA - Locked Rotor Amps - based on full winding (x-line) start units. YLRA for wye-delta starters is ~1/3 of LRA of x-line units.
9. VOLTAGE UTILIZATION RANGE:
Rated Voltage Utilization Range
200/60/3 180-220
230/60/3 208-254
380/60/3 342-418
460/60/3 414-506
575/60/3 516-633
400/50/3 360-440
10. A separate 115/60/1, 20 amp or 220/50/1, 15 amp customer provided power connection is needed to power the evaporator heaters (1640 watts).
11. If factory circuit breakers are supplied with the chiller, then these values represent Maximum Overcurrent Protection (MOP).
12. When the circuit breaker option is ordered, two circuit breakers will be provided (one per circuit) for both single and dual point power.