Trane RLC-PRC006-EN Beverage Dispenser User Manual


 
27RLC-PRC006-EN
Performance
Data
Full Load
Performance
Table P-5 (Continued) 50 Hz Standard Efficiency Machines in English Units
Condenser Entering Air Temperature (F)
85 95 105 115
Evaporator
Leaving Water Unit Size
Temperature (F) Model RTAC Tons kW input EER Tons kW input EER Ton kW input EER Tons kW input EER
140 STD 152.8 153.7 11.1 142.3 167.8 9.5 131.4 183.5 8.1 112.7 184.4 6.9
155 STD 167.1 170.2 11.0 155.6 185.3 9.4 143.7 202.1 8.0 123.4 202.7 6.9
170 STD 181.5 187.0 10.9 169.0 203.0 9.4 156.1 220.8 8.0 134.2 221.2 6.9
185 STD 200.7 204.0 11.0 187.3 221.5 9.5 173.3 240.9 8.1 148.1 238.7 7.0
200 STD 220.3 221.3 11.1 205.8 240.1 9.6 190.8 261.2 8.2 162.1 256.1 7.1
46 250 STD 259.7 263.0 11.1 242.6 286.6 9.5 224.8 312.9 8.1 191.0 308.5 7.0
275 STD 290.7 298.3 10.9 271.3 323.7 9.4 251.2 352.0 8.1 211.9 342.6 7.0
300 STD 329.8 334.5 11.0 308.3 362.6 9.6 286.0 394.0 8.2 239.3 377.8 7.1
350 STD 359.1 374.1 10.7 334.7 406.0 9.3 309.5 441.6 7.9 263.8 436.9 6.8
375 STD 396.2 408.4 10.9 370.1 443.2 9.4 342.9 482.0 8.0 292.1 474.7 6.9
400 STD 436.9 445.5 11.0 408.4 482.8 9.5 378.8 524.6 8.1 318.5 506.6 7.1
140 STD 157.8 157.0 11.3 147.0 171.2 9.7 135.8 187.0 8.2 113.5 180.6 7.1
155 STD 172.5 173.9 11.1 160.6 189.1 9.6 148.4 206.0 8.1 124.4 199.2 7.1
170 STD 187.3 191.2 11.0 174.5 207.3 9.5 161.2 225.2 8.1 134.9 216.5 7.0
185 STD 207.1 208.6 11.1 193.3 226.2 9.6 178.9 245.9 8.2 149.4 234.9 7.2
200 STD 227.3 226.3 11.3 212.4 245.4 9.7 196.9 266.8 8.3 163.3 251.5 7.3
48 250 STD 268.0 268.6 11.2 250.4 292.4 9.6 231.0 316.8 8.2 193.4 304.7 7.2
275 STD 299.8 304.9 11.0 279.9 330.5 9.5 258.2 356.9 8.2 213.7 336.9 7.2
300 STD 340.3 342.1 11.2 318.2 370.5 9.7 291.3 394.3 8.3 242.3 373.4 7.3
350 STD 370.6 382.4 10.9 345.5 414.5 9.4 319.6 450.4 8.0 266.4 430.3 7.0
375 STD 408.7 417.6 11.0 381.9 452.6 9.5 354.0 491.8 8.1 294.6 466.9 7.1
400 STD 450.8 455.7 11.1 421.5 493.5 9.6 385.8 525.1 8.3 320.8 497.3 7.3
140 STD 162.9 160.3 11.4 151.8 174.7 9.8 138.3 186.4 8.4 114.7 177.8 7.3
155 STD 177.9 177.7 11.2 165.8 193.0 9.7 150.6 204.4 8.3 125.3 195.3 7.2
170 STD 193.2 195.5 11.1 180.0 211.7 9.6 164.4 225.4 8.2 136.1 212.8 7.2
185 STD 213.6 213.3 11.2 199.4 231.1 9.7 181.5 244.4 8.4 150.6 230.5 7.4
200 STD 234.4 231.4 11.4 219.1 250.8 9.8 197.9 261.3 8.5 164.7 247.2 7.5
50 250 STD 276.4 274.3 11.3 258.3 298.4 9.8 232.9 311.6 8.4 194.4 298.0 7.4
275 STD 309.1 311.7 11.1 288.6 337.5 9.6 259.7 350.1 8.4 216.1 332.7 7.3
300 STD 350.8 349.8 11.3 328.1 378.7 9.8 292.5 385.8 8.6 244.1 367.5 7.5
350 STD 382.1 390.9 11.0 356.3 423.2 9.5 323.1 445.2 8.2 268.9 423.6 7.2
375 STD 421.4 426.9 11.1 393.8 462.3 9.6 356.0 482.5 8.3 297.3 459.3 7.3
400 STD 464.9 466.1 11.2 434.7 504.4 9.7 387.5 513.9 8.5 323.3 489.4 7.4
Notes:
1. Ratings based on sea level altitude and evaporator fouling factor of 0.00010.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kW input is for compressors only.
4. EER = Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 10°F.
6. Ambient temperatures 115°F and greater reflect the high ambient condenser option.
7. Interpolation between points is permissible. Extrapolation is not permitted.
8. Rated in accordance with ARI Standard 550/590-98.