Electrical
Data
Table E-2 (Continued) Unit Electrical Data for High Efficiency at Std. Ambient Operation
Unit Wiring Motor Data
# of Max. Fuse, HACR Rec. Time Compressor (Each) Fans (Each)
Unit Rated Power MCA (3) Breaker or MOP (11) Delay or RDE (4) RLA (5) XLRA (8) YLRA (8) Qty. Control
Size Voltage Conns (1) Ckt 1/Ckt 2 Ckt 1/Ckt 2 Ckt 1/Ckt 2 Qty Ckt 1/Ckt 2 Ckt 1/Ckt 2 Ckt 1/Ckt 2 Ckt 1/Ckt 2 kW FLA kW (7)
RTAC 400/50/3 1 819 1000 1000 4 189-189-160-160 1089-1089-896-896 354-354-291-291 26 1.5 2.8 1.59
375 400/50/3 2 465/394 600/500 600/450 4 189-189/160-160 1089-1089/896-896 254-254/291-291 14/12 1.5 2.8 1.59
200/60/3 1 NA
200/60/3 2 931/931 1200/1200 1200/1200 4 373-373/373-373 NA 701-701/701-701 14/14 1.5 6.5 1.59
230/60/3 1 NA
230/60/3 2 820/820 1000/1000 1000/1000 4 324-324/324-324 NA 571-571/571-571 14/14 1.5 6.5 1.59
RTAC 380/60/3 1 NA
400 380/60/3 2 490/490 600/600 600/600 4 196-196/196-196 1060-1060/1060-1060 345-345/345-345 14/14 1.5 3.5 1.59
460/60/3 1 773 800 800 4 162-162-162-162 878-878-878-878 285-285-285-285 28 1.5 3.0 1.59
460/60/3 2 407/407 500/500 450/450 4 162-162/162-162 878-878/878-878 285-285/285-285 14/14 1.5 3.0 1.59
575/60/3 1 623 700 700 4 130-130-130-130 705-705-705-705 229-229-229-229 28 1.5 2.5 1.59
575/60/3 2 328/328 450/450 400/400 4 130-130/130-130 705-705/705-705 229-229/229-229 14/14 1.5 2.5 1.59
400/50/3 1 882 1000 1000 4 189-189-189-189 1089-1089-1089-1089 354-354-354-354 28 1.5 2.8 1.59
400/50/3 2 465/465 600/600 600/600 4 189-189/189-189 1089-10
89/1089-1089 354-354/354-354 14/14 1.5 2.8 1.59
Notes:
1. As standard, 140-250 ton (60 Hz) units and 140-200 ton (50 Hz) units have single point power connections. Optional dual point power connections are available. As standard,
275-500 ton (60 Hz) units and 250-400 ton (50 Hz) units have dual point power connections. Optional single point power connections are available on 380V, 460V, 575 V/60 Hz and
400V/50 Hz units.
2. Max Fuse or HACR type breaker = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA, plus the sum of the condenser fan FLA per NEC 440-22.
Use FLA per circuit, NOT FLA for the entire unit).
3. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of the second compressor RLA plus the sum of the condenser fans FLAs per NEC 440-33.
4. RECOMMENDED TIME DELAY OR DUAL ELEMENT (RDE) FUSE SIZE: 150 percent of the largest compressor RLA plus 100 percent of the second compressor RLA and the sum of the condenser
fan FLAs.
5. RLA - Rated Load Amps - rated in accordance with UL Standard 1995.
6. Local codes may take precedence.
7. Control kW includes operational controls only. Does not include evaporator heaters.
8. XLRA - Locked Rotor Amps - based on full winding (x-line) start units. YLRA for wye-delta starters is ~1/3 of LRA of x-line units.
9. VOLTAGE UTILIZATION RANGE:
Rated Voltage Utilization Range
200/60/3 180-220
230/60/3 208-254
380/60/3 342-418
460/60/3 414-506
575/60/3 516-633
400/50/3 360-440
10. A separate 115/60/1, 20 amp or 220/50/1, 15 amp customer provided power connection is needed to power the evaporator heaters (1640 watts).
11. If factory circuit breakers are supplied with the chiller, then these values represent Maximum Overcurrent Protection (MOP).
12. When the circuit breaker option is ordered, two circuit breakers will be provided (one per circuit) for both single and dual point power.