33RLC-PRC006-EN
Table P-12 - ARI Part-Load Performance for
50 Hz High Efficiency
Machines in English units
Unit Size % Load Tons EER IPLV
RTAC 100 144.7 10.3
140 75 108.5 11.4 14.1
High 50 72.3 16.2
25 36.2 16.2
RTAC 100 157.4 10.1
155 75 118.1 11.4 14.1
High 50 78.7 16.1
25 39.3 17.0
RTAC 100 170.2 10.0
170 75 127.6 11.5 13.9
High 50 85.1 15.8
25 42.5 15.8
RTAC 100 189.2 10.1
185 75 141.9 11.8 14.4
High 50 94.6 16.4
25 47.3 16.6
RTAC 100 208.7 10.3
200 75 156.5 11.0 13.8
High 50 104.3 16.0
25 52.2 15.6
RTAC 100 245.5 9.9
250 75 182.6 13.1 15.6
High 50 121.8 16.8
25 60.9 20.1
RTAC 100 275.5 10.1
275 75 205.0 13.3 15.2
High 50 136.7 16.3
25 68.9 18.3
RTAC 100 310.8 10.2
300 75 230.8 13.4 14.4
High 50 153.9 14.1
25 77.7 19.4
RTAC 100 337.9 9.9
350 75 253.3 13.1 14.9
High 50 168.9 15.6
25 84.5 19.1
RTAC 100 375.9 10.0
375 75 280.6 13.2 15.2
High 50 187.1 16.1
25 93.6 19.7
RTAC 100 413.9 10.1
400 75 307.8 13.3 15.1
High 50 205.3 15.8
25 102.6 19.6
Performance
Data
Part Load
Performance
Table P-11 - ARI Part-Load Performance for
50 Hz Standard Efficiency
Machines in English units
Unit Size % Load Tons EER IPLV
RTAC 100 137.6 9.4
140 75 103.2 10.7 13.4
Standard 50 68.8 15.4
25 34.4 15.8
RTAC 100 150.5 9.3
155 75 112.9 10.8 13.5
Standard 50 75.3 15.3
25 37.6 16.5
RTAC 100 163.3 9.2
170 75 122.6 10.9 13.3
Standard 50 81.8 15.0
25 40.9 15.4
RTAC 100 181.3 9.4
185 75 135.9 11.2 13.8
Standard 50 90.7 15.7
25 45.3 16.1
RTAC 100 199.3 9.5
200 75 149.5 10.5 13.2
Standard 50 99.7 15.3
25 49.8 15.0
RTAC 100 234.8 9.4
250 75 174.6 12.6 15.1
Standard 50 116.4 16.0
25 58.2 20.7
RTAC 100 262.7 9.3
275 75 195.5 12.5 14.4
Standard 50 130.3 15.6
25 65.7 17.1
RTAC 100 298.6 9.5
300 75 221.7 12.7 13.8
Standard 50 147.8 13.8
25 74.7 18.2
RTAC 100 324.0 9.2
350 75 242.8 12.4 14.3
Standard 50 161.9 14.9
25 81.0 19.4
RTAC 100 358.4 9.3
375 75 267.4 12.5 14.7
Standard 50 178.3 15.4
25 89.2 20.1
RTAC 100 395.5 9.4
400 75 294.1 12.7 14.6
Standard 50 196.1 15.1
25 98.1 19.9
Notes:
1. IPLV values are rated in accordance with ARI Standard
550/590-98.
2. EER and IPLV values include compressors, condenser
fans and control kW.