Trane RLC-PRC006-EN Beverage Dispenser User Manual


 
RLC-PRC006-EN50
Electrical
Connections
Table E-5 (Continued) Customer Wire Selection for Dual Point Units
Wire Selection Size Wire Selection Size Wire Selection Size Wire Selection Size
to Main Terminal Block to Main Terminal Block to Disconnect (2) to Circuit Breaker (2)
XL Starter YD Starter
Unit Rated Connector Wire Range Connector Wire Range Connector Wire Range Connector Wire Range
Size Voltage Ckt 1 / Ckt 2 Ckt 1 / Ckt 2 Ckt 1 / Ckt 2 Ckt 1 / Ckt 2
RTAC 400V-50Hz Lug Size G/Lug Size G Lug Size N/Lug Size G Lug Size B/Lug Size B Lug Size B/Lug Size B
375 STD
RTAC 400V-50Hz Lug Size G/Lug Size G Lug Size N/Lug Size G Lug Size B/Lug Size B Lug Size B/Lug Size B
375 HIGH
200V-60Hz NA Lug Size L/Lug Size L Lug Size B/Lug Size B Lug Size B/Lug Size B
230V-60Hz NA Lug Size L/Lug Size L Lug Size B/Lug Size B Lug Size B/Lug Size B
RTAC 380V-60Hz Lug Size G/Lug Size G Lug Size G/Lug Size G Lug Size H/Lug Size H Lug Size H/Lug Size H
400 460V-60Hz Lug Size L/Lug Size L Lug Size M/Lug Size M Lug Size B/Lug Size B Lug Size B/Lug Size B
STD 575V-60Hz Lug Size I or E/Lug Size I or E Lug Size F/Lug Size F Lug Size A/Lug Size A Lug Size A/Lug Size A
400V-50Hz Lug Size G/Lug Size G Lug Size N/Lug Size G Lug Size B/Lug Size B Lug Size B/Lug Size B
200V-60Hz NA Lug Size L/Lug Size L Lug Size B/Lug Size B Lug Size B/Lug Size B
230V-60Hz NA Lug Size L/Lug Size L Lug Size B/Lug Size B Lug Size B/Lug Size B
RTAC 380V-60Hz Lug Size G/Lug Size G Lug Size G/Lug Size G Lug Size H/Lug Size H Lug Size H/Lug Size H
400 460V-60Hz Lug Size L/Lug Size L Lug Size M/Lug Size M Lug Size B/Lug Size B Lug Size B/Lug Size B
HIGH 575V-60Hz Lug Size I or E/Lug Size I or E Lug Size F/Lug Size F Lug Size A/Lug Size A Lug Size A/Lug Size A
400V-50Hz Lug Size G/Lug Size G Lug Size N/Lug Size G Lug Size B/Lug Size B Lug Size B/Lug Size B
200V-60Hz NA Lug Size L/Lug Size L Lug Size B/Lug Size B Lug Size B/Lug Size B
RTAC 230V-60Hz NA Lug Size L/Lug Size L Lug Size B/Lug Size B Lug Size B/Lug Size B
450 380V-60Hz Lug Size G/Lug Size G Lug Size G/Lug Size G Lug Size B/Lug Size H Lug Size B/Lug Size H
STD 460V-60Hz Lug Size L/Lug Size L Lug Size N/Lug Size M Lug Size B/Lug Size B Lug Size B/Lug Size B
575V-60Hz Lug Size G/Lug Size G Lug Size N/Lug Size F Lug Size B/Lug Size A Lug Size B/Lug Size A
200V-60Hz NA Lug Size L/Lug Size L Lug Size B/Lug Size B Lug Size B/Lug Size B
RTAC 230V-60Hz NA Lug Size L/Lug Size L Lug Size B/Lug Size B Lug Size B/Lug Size B
500 380V-60Hz Lug Size G/Lug Size G Lug Size G/Lug Size G Lug Size B/Lug Size B Lug Size B/Lug Size B
STD 460V-60Hz Lug Size L/Lug Size L Lug Size N/Lug Size N Lug Size B/Lug Size B Lug Size B/Lug Size B
575V-60Hz Lug Size G/Lug Size G Lug Size F/Lug Size L Lug Size B/Lug Size A Lug Size B/Lug Size A
Lug Size A = (1) 4/0 to 600 MCM per phase
Lug Size B = (4) 4/0 to 500 MCM per phase
Lug Size C = (1) #3 to 350 MCM per phase
Lug Size D = (1) #2 to 500 MCM per phase
Lug Size E (5) = (2) 1/0 to 250 MCM per phase
Lug Size F = (2) #4 to 500 MCM per phase
Lug Size G = (2) #2 to 600 MCM per phase
Lug Size H = (2) 400 to 500 MCM per phase
Lug Size I (5) = (1) #2 to 750 MCM per phase
Lug Size J = (1) 250 to 500 MCM per phase
Lug Size K = (2) 3/0 to 350 MCM per phase
Lug Size L = (4) #2 to 600 MCM per phase
Lug Size M = (2) #4 to 600 MCM per phase
Lug Size N = (2) #2 to 600 MCM per phase
Lug Size O = (1) #2 to 250 MCM per phase
1. As standard, 140-250 ton (60 Hz) units and 140-200 ton (50 Hz) units have single point power connections. Optional dual point power connections are available. As standard,
275-500 ton (60 Hz) units and 250-400 ton (50 Hz) units have dual point power connections. Optional single point power connections are available on 380V, 460V, 575 V/60 Hz and
400V/50 Hz units.
2. Non-fused unit disconnect and circuit breaker are optional.
3. Copper wire only, sized per N.E.C., based on nameplate minimum circuit ampacity (MCA).
4. Circuit Breaker sizes are for factory mounted only. Field installed circuit breakers need to be sized using HACR breaker recommendations from Table E-1.
5. A single, dual-rated lug is associated with the Lug Size E or I designation. Each phase of the lug has a single, oval-shaped hole, into which a single #2 to 750 MCM wire OR two 1/
0 to 250 MCM wires can be inserted.