York YT Water Dispenser User Manual


 
FORM 160.55-O1 (604)
115
YORK INTERNATIONAL
Model 1220
- ConÞ gure Menu
Baud= 1200
Data Bits = 8
Stop Bits = 1
Hshake = Busy-Line
Cols = 32
Invert = No
Font = 5 x 8
Mag = None
- Custom Menu
Auto Seq = No
Zero = 0
Pound sign = #
_(Underscore)
Busy invert = no
Online/ofß ine = yes
Ext Ch Set = no
Print ready = yes
Set Clock = not used
Reset Seq = not used
• SEIKO
DipSW1-1 = off Input-Serial
1-2 = on Printing speed high
1-3 = on Auto loading - on
1-4 = off Auto LF - off
1-5 = on Setting Command - Enable
1-6 = off Printing density - 100%
1-7 = on Printing density - 100%
1-8 = on Printing, density - 100%
DipSW 2-1= on Printing Columns - 40
2-2 = on User Font Back-up - on
2-3 = on Character Select - normal
2-4 = off Zero - slash
2-5 = on International character set -
American
2-6 = on International character set -
American
2-7 = on International character set -
American
2-8 = off International character set -
American
DipSW 3-1= on Data length - 8 bits
3-2 = on Parity Setting - no
3-3 = on Parity condition - odd
3-4 = on Busy control - H/W busy
3-5 = on Baud rate select - 1200*
3-6 = off Baud rate select - 1200*
3-7 = on Baud rate select - 1200*
3-8 = off Baud rate select - 1200*
* Settings shown for 1200 Baud. Other Baud rates can
be selected. Refer to Printer manufacturer’s manual
supplied with Printer.
CONTROL CENTER SETUP
Chiller ID
Access Level Required: OPERATOR or Higher
Using the COMMS Screen, assign an IdentiÞ cation
number to the chiller. This number will appear at the
top of each report.
Printer Setup
Access Level Required: OPERATOR or Higher
Using the COMMS Screen, the Control Center must be
conÞ gured to transmit data in the same format as the
Printer is conÞ gured to receive the data. The following
values must be entered.
• Baud Rate - Set as desired. Value selected must be
the same as Printer conÞ guration above.
• Data Bits - 8
• Parity - None
• Stop Bits - 1
Printer Type
Access Level required: OPERATOR or Higher
Using the PRINTER Screen, the actual Printer type con-
nected to the Control Center must be entered. Se lec tion
determines the control codes that are sent to the Printer.
These codes determine such things as lines per inch,
character width and general formatting. Avail able selec-
tions are: Okidata, Weigh-Tronix and Seiko.
Automatic Data Logging
Access Level required: OP ER A TOR or Higher.
If automatic data logging is desired, a Status Report can
be automatically printed at a speciÞ ed interval be gin ning
at a speciÞ ed time, using the PRINTER Screen. The
interval is programmable over the range of 1 minute
to 1440 minutes in 1 minute increments. The Þ rst print
will occur at the programmed START time and occur at
the programmed OUTPUT INTERVAL thereafter. The
time remaining until the next print is displayed on the
PRINTER Screen.
• Automatic Printer Logging - Enables and disables
au to mat ic data logging
• Log Start Time - Enter the time the Þ rst print is
de sired.
• Output Interval - Enter the desired interval be tween
prints.
3