York YT Water Dispenser User Manual


 
FORM 160.55-O1 (604)
87
YORK INTERNATIONAL
PROGRAMMABLE
Primary Trigger
Access Level Required: OPERATOR
Selects the Þ rst parameter to be evaluated. Selection is
made from the Slot Numbers listing on the Trend Com-
mon Slots Screen or the Master Slot Numbers List in
this book. Setting this slot number to zero disables the
Primary Trigger.
Primary Operator
Access Level Required: OPERATOR
Selects the comparator for the Primary Trigger’s re la -
tion ship to the Primary Test. If the Primary Trigger is
an analog value, selections are: <, <=, =, =>, >. If the
Primary Trigger is a digital event, selections are: Equal
To, Not Equal To.
Primary Test
Access Level Required: OPERATOR
Selects the value or condition that the Primary Trigger
is compared to. Selection ranges from the Primary Trig-
ger minimum value to the Primary Trigger maximum
value.
Trigger Action
Access Level Required: OPERATOR
Selects whether the trend data collection will Start or
Stop when the Trigger comparisons are true. If set to
Start, data collection will stop after one screen of data
is collected.
Trigger Delay
Access Level Required: OPERATOR
Allows the data collection start or stop to be delayed
after the Triggers evaluate as true. The delay is se-
lect able from 1 to 864000 seconds (10 days). Display
is in days, hours, minutes and seconds. The delay timer
be gins when the triggers evaluate as true. If the Trigger
Action is set to Start, data collection will begin after the
triggers evaluate as true and the delay timer has elapsed.
If the Trigger Action is set to Stop, data collection will
stop after the Triggers evaluate as true and the delay
timer has elapsed.
Primary to Secondary Operator
Access Level Required: OPERATOR
Selects whether the Primary Trigger, Secondary Trig-
ger or both have to be true in order to start or stop data
collection. Selections are AND, OR, XOR and None. If
NONE is selected, the Secondary Trigger is disabled.
Data collection will start/stop (as selected with Trigger
Action) when:
• If AND selected: Both Primary AND Sec ond ary are
true
• If OR selected: Either Primary OR Secondary (or
both) are true
• If XOR selected: Either Primary OR Sec ond ary (but
not both) are true
Secondary Trigger
Access Level Required: OPERATOR
Selects the second parameter to be evaluated. Se lec tion
is made from the Slot Numbers listing on the Trend
Common Slots Screen or the Master Slot Numbers List
in this book. Setting this slot number to zero disables
the Secondary Trigger.
Secondary Operator
Access Level required: OPERATOR
Selects the comparator for the Secondary Trigger’s re la -
tion ship to the Secondary Test. If the Secondary trig ger
is an Analog value, selections are: <, <=, =, =>, >. If
the Secondary Trigger is a digital event, selections are:
Equal To, Not Equal To.
Secondary Test
Access Level Required: OPERATOR
Selects the value or condition that the Secondary Trig ger
is compared to. Selection ranges from the Sec ond ary Trig-
ger minimum to the Secondary Trig ger max i mum.
NAVIGATION
HOME
Causes an instant return to the Home Screen.
TREND SETUP
Causes an instant return to the Trend Setup Screen.
2