York YT Water Dispenser User Manual


 
FORM 160.55-O1 (604)
91
YORK INTERNATIONAL
MASTER SLOT NUMBERS LIST FOR USE WITH TREND FEA TURE
SLOT
NO.
DESCRIPTION
256 System: Chiller State
257 System: Coastdown Time Remaining
258 System: Prelube Time Remaining
259 System: Are Safety Shut down Contacts Closed
260 System: Are Cy cling Shutdown Contacts Closed
261 System: Are An tic i pa to ry Alarm Contacts Closed
262 System: Operating Hours
264 System: Number of Starts
265 System: Is Stop Switch Closed
266 System: Is Start Switch Closed
267 System: Is Remote Ready to Start
280 External Contact: Is Re mote Stop Closed
281 External Contact: Is Re mote Start Closed
282 External Contact: Is MultiUnit Cycling Closed
283 External Contact: Is Re mote Cycling Closed
284 External Contact: Is Aux il ia ry Safety Open
285 Jumper: Is Anti-Recycle Enabled
286 Jumper: Coastdown Operation
287 Jumper: Is Di ag nos tics Enabled
288 Jumper: Liquid Type
289 Jumper: Chilled Liq uid Pump Operation
290 Jumper: Motor Type
291 Jumper: Power Fail ure Restart
292 Jumper: Pre-Run Op er a tion
293 Jumper: Refrigerant Selection
294 Jumper: VSD Motor Sup ply Line Frequency
304 Options: Control Mode
305 Options: System Lan guage
307 Options: Display Mode
512 Sched: Is Schedule Enabled
1280 Pre-Rotation Vanes: Is Motor Switch Closed
1281 Pre-Rotation Vanes: Position
1282 Pre-Rotation Vanes: Are Vanes Opening
1283 Pre-Rotation Vanes: Are Vanes Closing
1284 Pre-Rotation Vanes: Are Vanes Holding
1285 Pre-Rotation Vanes: Control Mode
1296 Discharge: Temperature
1536 Oil: Differential Pressure
1537 Oil: Sump Temperature
1538 Oil Pump: Control Mode
1539 Oil Pump: Is Pump On
1540 Oil Pump: Manual Time Left
SLOT
NO.
DESCRIPTION
1792 Leaving Chilled Liquid: Temperature
1793 Leaving Chilled Liquid: Temperature Differential
1794 Leaving Chilled Liquid: Is Flow Switch Closed
1795 Leaving Chilled Liquid: Is Pump On
1796 Leaving Chilled Liquid: Local Temperature Setpoint
1797 Leaving Chilled Liquid: Remote Analog Tem per a ture
Setpoint
1798 Leaving Chilled Liquid: Remote ISN Temperature
Setpoint
1799 Leaving Chilled Liquid: Remote Modem Tem per a ture
Setpoint
1800 Leaving Chilled Liquid: Selected Temperature
Setpoint
1801 Leaving Chilled Liquid: Control Sensitivity
1802 Leaving Chilled Liquid: Remote Temperature
Range
1803 Leaving Chilled Liquid: Restart Temperature Off set
1804 Leaving Chilled Liquid: Restart Temperature
Setpoint
1805 Leaving Chilled Liquid: Shutdown Temperature Off-
set
1806 Leaving Chilled Liquid: Shutdown Temperature
Setpoint
1807 Return Chilled Liquid: Temperature
1808 Evaporator: Pressure
1809 Evaporator: Saturation Temperature
1810 Evaporator: Small Temperature Difference
1811 Evaporator: Is Refrigerant Sensor Present
1812 Evaporator: Refrigerant Temperature
1813 Evaporator: Delta P / P
1814 Evaporator: Brine Low Cutout
1815 Smart Freeze Protection: Is Control Enabled
1818 Leaving Chilled Liquid: Remote Digital Tem per a ture
Setpoint
2048 Leaving Condenser Liquid: Temperature
2049 Leaving Condenser Liquid: Is Flow Switch Closed
2050 Leaving Condenser Liquid: Is Pump On
2051 Return Condenser Liquid: Temperature
2052 Condenser: Pressure
2053 Condenser: Saturation Temperature
2054 Condenser: Small Temperature Difference
2057 Condenser: Is High Pressure Switch Closed
2058 Condenser: High Pressure Warning Threshold
2