if the SURGE WINDOW COUNT is less than or
equal to the COUNT LIMIT, this message and load
inhibit are au to mat i cal ly cleared. Al ter nat ing with
this message is “Warning – Excess Surge De tect ed”
that continues after the 10 minute pe ri od has elapsed
until man u al ly cleared with the Warning Reset key.
See Hot Gas By pass and Variable Speed Drive ex-
ception above.
• If both the SHUTDOWN and EXTENDED RUN
setpoint are Enabled, the 10 minute Extended RUN
mode is in voked as described above. However, if the
SURGE WIN DOW COUNT exceeds the COUNT
LIMIT at the completon of the 10 minute extended
run period, a safety shutdown is per formed and
“Surge Protection – Excess Surge” is dis played. See
Hot Gas By pass and Variable Speed Drive exception
above.
Surge Sensitivity
Access Level Required: SERVICE
Allows the user to deÞ ne the surge detection sen si tiv i ty.
Se lect able over the range of 0.3 to 1.3; default 0.3. The
smaller the number, the greater the sensitivity.
Clear Surge Count
Access Level Required: ADMIN
Allows user to set the Total Surge Count to zero.
NAVIGATION
Home
Access Level Required: VIEW
Causes an instant return to the Home Screen
Compressor
Access Level Required: VIEW
Causes an instant return to the Compressor Screen.