SYSTEM SCREEN
OVERVIEW
This screen gives a general overview of common chill er
parameters for both shells.
DISPLAY ONLY
Discharge Temperature
Displays the temperature of the refrigerant in its gas-
eous state at discharge of the compressor as it travels
to the condenser.
Chilled Liquid Temperature - Leaving
Displays the temperature of the liquid as it leaves the
evaporator.
Chilled Liquid Temperature - Return
Displays the temperature of the liquid as it enters the
evaporator.
Chilled Liquid Temperature - Setpoint
Displays the active temperature setpoint to which the
chiller is controlling the evaporator liquid. This value
could come from a 0-20mA or 4-20mA, 0-10VDC or 2-
10VDC input in An a log Remote mode, PWM signal in
Digital Remote mode, MicroGateway interface in ISN
mode or a locally pro grammed value in local mode.
Evaporator Pressure
Displays the present refrigerant pressure in the evap o ra tor.
Evaporator Saturation Temperature
Displays the present saturation temperature in the
evap o ra tor.
Condenser Liquid Temperature - Leaving
Displays the temperature of the liquid as it leaves the
condenser.
Condenser Liquid Temperature - Return
Displays the temperature of the liquid as it enters the
condenser.
Condenser Pressure
Displays the refrigerant pressure in the condenser.
Condenser Saturation Temperature
Displays the saturation temperature in the condenser.
Oil Sump Temperature
Displays the temperature of the oil in the sump.
Oil Pressure
Displays the pressure differential between the pump oil
pressure transducer and the sump oil pressure trans duc er.
If either of the transducers used to cal cu late this dif fer -
en tial is out of range, the display Þ eld will show XX.X.
% Full Load Amps
This displays the percentage of full load amps utilized
by the system.