Using FINS Applications Section 6-5
6-5 Using FINS Applications
6-5-1 CX-Programmer (CX-Server)
The following examples show how to connect online from a CX-Programmer
on an Ethernet network to a PLC on the Ethernet network.
System Configuration Example 1: No Routing
In this example, an online connection is made by FINS/UDP to a PLC on an
Ethernet network (PLC1 in the diagram below) from a CX-Programmer/CX-
Integrator connected to the Ethernet network.
Conditions
FINS/UDP method
IP address conversion: Automatic generation method (dynamic)
CX-Programmer's Change PLC Dialog Box
CX-Programmer/CX-Integrator
Ethernet (Network address: None)
Ethernet port
Target: PLC1
Ethernet Unit
IP address: 192.168.250.1
FINS/UDP method
Node number: 1
IP address conversion: Automatic
generation method (dynamic)
Ethernet Unit node number: 2
Ethernet Unit IP address: 192.168.250.2
Settings for target PLC (PLC1)'s Change PLC Dialog Box Setting
PLC name PLC1
Network classification Ethernet
Network Tab FINS transmission source address 0
FINS destination Network number 0
Node address 2
Frame length 2,000 bytes
Response monitor time 2 seconds
Driver Tab Workstation node address 1
Automatic generation method Not selected
IP address 192.168.250.2
(Ethernet Unit IP
address)
Port number 9600