Carrier 17/19EX Refrigerator User Manual


 
Example 11 — Maintenance (Maint02) Display Screen
To access this display from the LID default screen:
1. Press MENU.
2. Press SERVICE.
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT.
5. Scroll down to highlight MAINT02.
6. Press SELECT.
Note: Overriding is not supported on this maintenance screen. Active overrides show the associated point in
alert (*). Only values with capital letter reference point names are variables available for read opera-
tion.
† Information is applicable to hermetic machines only.
Table 2, Example 11 — Maintenance (Maint02) Display Screen
Description Range/Status Units
Reference
Point Name
OVERRIDE/ALERT STATUS
MOTOR WINDING TEMP
Override Threshold
CONDENSER PRESSURE
Override Threshold
EVAPORATOR REFRIG TEMP
Override Threshold
DISCHARGE TEMPERATURE
Alert Threshold
BEARING TEMPERATURE
Alert Threshold
–40-245 (–40-118)
150-200 (66-93)
-6.7-420 (-42-2896)
90-245 (621-1689)
–40-245 (–40-118)
2-45 (1-7.2)
–40-245 (–40-118)
125-200 (52-93)
–40-245 (–40-118)
175-185 (79-85)
DEG F (DEG C)
DEG F (DEG C)
PSI (kPa)
PSI (kPa)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
MTRW
mt
over
CRP
cp
over
ERT
rt
over
CMPD
cd
alert
MTRB
tb
alert