* If a machine configuration other than 2-pass, 150 psig (1034 kPa), NIH waterbox configuration is used, refer to the Additional Cooler
Weights or Additional Condenser Weights tables, Table 11 and Table 13 to obtain the additional dry and water weights that must be
added to the values shown in this table.
† Cooler and condenser weights shown are based upon 2-pass, nozzle-in-head (NIH) waterboxes with 150 psig (1034 kPa) covers.
Includes components attached to cooler, but does not include suction/discharge, elbow, or other interconnecting piping.
** Dry weight includes all components attached to economizer: Covers, float valves, brackets, control center (31 lb [14 kg]), and power
panel (20 lb [9 kg]). Dry weight does not include compressor weight, motor weight, or pumpdown condensing unit weight. The pumpdown
condensing unit weight is 210 lb (95 kg). For compressor and motor weights, refer to Table 12.
†† Operating weight includes dry weight, refrigerant weight, and water weight.
Table 10 — 17/19EX Heat Exchanger, Economizer/Storage Vessel, Piping, and Pumpout Unit Weights*
(Page 1 of 2)
Cooler
Size
Cooler Total Weight Cooler Charge
Economizer/
Storage
Vessel
Economizer
Refrigerant
Miscellaneous
Piping
Pumpout
Unit
Dry** Operating
††
Refrigerant Water
lb kg lb kg lb kg lb kg
lb kg lb kg lb kg lb kg
41
21,674 9 831 26,120 11 848 2,005 909 2,441 1 107
7,169 3 525 610 277 1,095 497
210 95
42
22,019 9 988 26,736 12 127 2,142 972 2,575 1 168
43
22,364 10 144 27,322 12 393 2,249 1 020 2,709 1 229
44
23,841 10 814 29,836 13 533 2,710 1 229 3,285 1 490
45
25,032 11 354 30,790 13 966 2,752 1 248 3,006 1 363
7,900 3 583 844 383 1,149 521
46
25,529 11 580 31,658 14 360 2,937 1 332 3,192 1 448
47
26,025 11 805 32,496 14 740 3,093 1 403 3,378 1 532
48
28,153 12 770 36,053 16 353 3,727 1 691 4,173 1 893