Carrier 17/19EX Refrigerator User Manual


 
Flow Switches (Field Supplied)
Operate water pumps with machine off. Manually reduce water flow and observe switch for proper cutout.
Safety shutdown occurs when cutout time exceeds 3 seconds.
Starter Acceleration Time
(Determined by inrush
current going below 100%
compressor motor load)
>
45 seconds For machines with reduced voltage
mechanical and solid-state starters
>
10 seconds For machines with full voltage starters
(Configured on Service1 table)
Starter Transition
>
75 seconds Reduced voltage starters only
Condenser Freeze
Protection
Energizes condenser pump relay if
condenser refrigerant temperature or
condenser entering water tempera-
ture is below the configured con-
denser freeze point temperature.
Deenergizes when the temperature is
5 F (3 C) above condenser freeze
point temperature.
CONDENSER FREEZE POINT config-
ured in Service01 table with a default
seting of 34 F (1 C).
Impeller Clearance
Displacement switch open Thrust movement excessive
Motor Leak Detector*
Water from motor cooling is leaking Water sensors are installed only on
open-drive motors that use water cool-
ing. (Totally enclosed, water-to-air
cooled [TEWAC] motors)
Table 3 — Protective Safety Limits and Control Settings (Continued)
Monitored Parameter Limit Applicable Comments
Carrier Part No. HK06ZC033
* Applicable to open drive machines only.
Carrier Part No. HK06ZC001
Note: Dimensions in parenthesis are
in millimeters
NO ADJUSTMENTS ARE TO BE MADE ON THIS
SETSCREW! (FACTORY ADJUSTED ONLY)