Carrier 17/19EX Refrigerator User Manual


 
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
B. Timing Out or Timed Out
Primary Message Secondary Message Probable Cause/Remedy
Ready To Start In XX
Min
Unoccupied Mode Time schedule for PIC is unoccupied. Machines will
start only when occupied.
Ready To Start In XX
Min
Remote Contacts Open Remote contacts have stopped machine. Close con-
tacts to start.
Ready To Start In XX
Min
Stop Command In Effect Chiller START/STOP on Status01 manually forced to
stop. Release value to start.
Ready To Start In XX
Min
Recycle Restart Pending Machine in recycle mode.
Ready To Start
Unoccupied Mode Time schedule for PIC is UNOCCUPIED. Machine will
start when occupied. Make sure the time and date have
been set on the Service menu.
Ready To Start
Remote Contacts Open Remote contacts have stopped machine. Close con-
tacts to start.
Ready To Start
Stop Command In Effect Chiller START/STOP on Status01 manually forced to
stop. Release value to start.
Ready To Start In XX
Min
Remote Contacts Closed Machine timer counting down unit. Ready for start.
Ready To Start In XX
Min
Occupied Mode Machine timer counting down unit. Ready for start.
Ready To Start
Remote Contacts Closed Machine timers complete, unit start will commence.
Ready To Start
Occupied Mode Machine timers complete, unit start will commence.
Startup Inhibited
Loadshed In Effect CCN loadshed module commanding chiller to stop.
Ready To Start In XX
Min
Start Command In Effect Chiller START/STOP on Status01 has been manually
forced to start. Machine will start regardless of time
schedule or remote contact status.