Carrier 17/19EX Refrigerator User Manual


 
LID Operation and Menus (Figure 14, Figure 15, Figure 16, Figure 17, Figure 18,
Figure 19, and Figure 20)
General
The LID display will automatically revert to the default screen after 15 minutes if no
softkey activity takes place and if the machine is not in the Pumpdown mode
(Figure 14).
When not in the default screen, the upper right-hand corner of the LID always dis-
plays the name of the screen that you have entered (Figure 15).
The LID may be configured in English or SI units, through the LID configuration
screen.
Local Operation — By pressing the LOCAL softkey, the PIC is now in the LOCAL
operation mode and the control will accept modification to programming from the LID
only. The PIC will use the Local Time Schedule to determine machine start and stop
times.
CCN Operation — By pressing the CCN softkey, the PIC is now in the CCN operation
mode, and the control will accept modifications from any CCN interface or module
(with the proper authority), as well as the LID. The PIC will use the CCN time sched-
ule to determine start and stop times.
Click here for Figure 13 — Power Panel with Options (Hermetic Machine Shown)