Carrier 17/19EX Refrigerator User Manual


 
SERVICE1 TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Motor Temp Override
150 to 200
(66 to 93)
DEG F
(DEG C)
200
(93)
Cond Pressure Override 90 to 200 (620 to 1379)
psig
(kPa)
125 (862)
Refrig Override Delta T
2to5
(1 to 3)
DEG F
(DEG C)
3
(1.6)
Chilled Medium Water/Brine Water
Brine Refrig Trippoint
8to40
(–13.3 to 4)
DEG F
(DEG C)
33
(1)
Compr Discharge Alert
125 to 200
(52 to 93)
DEG F
(DEG C)
200
(93)
Bearing Temp Alert
165 to 210
(74 to 99)
DEG F
(DEG C)
210
(99)
Water Flow Verify Time 0.5 to 5 MIN 5
Oil Press Verify Time 15 to 300 SEC 15
Water/Brine Deadband
0.5 to 2.0
(0.3 to 1.1)
DEG F
(DEG C)
1.0
(0.6)
Recycle Restart Delta T
2.0 to 10
(1.1 to 5.5)
DEG F
(DEG C)
5
(2.8)
Recycle Shutdown Delta T
0.5 to 4.0
(0.27 to 2.2)
DEG F
(DEG C)
1.0
(0.6)
Surge Limit/HGBP Option
Surge=0/HGBP=1
0/1 0
Surge/HGBP Delta T1
0.5 to 15
(0.3 to 8.3)
DEG F
(DEG C)
1.5
(0.8)
Surge/HGBP Delta P1 30 to 170 (206 to 1172)
psi
(kPa)
50 (345)
Surge/HGBP Delta T2
0.5 to 15.0
(0.3 to 8.3)
DEG F
(DEG C)
10
(5.6)
Surge/HGBP Delta P2 30 to 170 (206 to 1172)
psi
(kPa)
85 (586)
Surge/HGBP Deadband
1to3
(0.6 to 1.6)
DEG F
(DEG C)
1
(0.6)
Surge Delta Percent Amps 10 to 50 % 25
Surge Time Period 1to5 MIN 2
Demand Limit Source
Amps=0/Load=1
0/1 0
Amps Correction Factor 1to8 3
CL-7