Carrier 17/19EX Refrigerator User Manual


 
LEGEND For Table 8, A - N
1CR
AUX — Compressor Start Contact OILPD — Oil Pressure
CA P — Compressor Current OILT — Oil Sump Temperature
CDFL — Condenser Water Flow PIC — Product Integrated Control
CHIL S S — Chiller Start/Stop PRS TRIP — Pressure Trip Contact
CMPD — Discharge Temperature PSIO — Processor Sensor Input/Output Module
CRP — Condenser Pressure RLA — Rated Load Amps
ERT — Evaporator Refrigerant Temperature RUN AUX — Compressor Run Contact
EVFL — Chilled Water Flow SMM — Starter Management Module
GV TRG — Target Guide Vane Position SPR PL — Spare Protective Limit Input
LID — Local Interface Device STR FLT — Starter Fault
MTRB — Bearing Temperature TXV — Thermostatic Expansion Valve
MTRW — Motor Winding Temperature V P — Line Voltage: Percent
V REF — Voltage Reference
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
A. Shutdown with ON/OFF/RESET-OFF
Primary Message Secondary Message Probable Cause/Remedy
Manually Stopped —
Press
CCN or Local to Start PIC in OFF mode; press the CCN or local softkey to
start unit.
Terminate Pumpdown
Mode
To Select CCN or Local Enter the Control Test table and select Terminate Lock-
out to unlock compressor.
Shutdown In Progress
Compressor Unloading Machine unloading before shutdown due to Soft Stop
feature.
Shutdown In Progress
Compressor Deenergized Machine compressor is being commanded to stop.
Water pumps are deenergized within one minute.
Ice Build
Operation Complete Machine shutdown from Ice Build operation.