Model 500/600
2.8 GAS LEAK TEST
Prior to turning the gas supply on, be sure the gas valve knob
on the gas control valve is in the OFF position.
After the piping and fittings have been installed, check for gas leaks. A
simple checking method is to turn on the gas and brush all connections
with a soap solution. If bubbles occur, it indicates escaping gas. In this
event, the piping connection must be redone.
2-9. GAS PRESSURE
REGULATOR SETTING
The gas pressure regulator on the automatic gas valve
is factory set as follows:
Natural: 3.5 inches water column (0.87 kPa)
Propane: 10.0 inches water column (2.49 kPa)
The gas pressure regulator has been set by Henny Penny and
is not to be adjusted by the user.
2-10. GAS PILOT & BURNER
LIGHTING AND
SHUTDOWN
PROCEDURE
1207 2-9
To avoid fire or explosion, never use a lighted match or
open flame to test for gas leaks. Ignited gas could
result in severe personal injury and/or property
damage.
Lighting Procedure - Solid State Ignition
1. The frypot should be cleaned per the instructions in Section 3.
2. The frypot must be filled to the proper level with shortening.
Refer to Filling or Adding Shortening Section.
3. Turn main power switch to OFF position.
4. Turn the gas valve knob counterclockwise to the OFF position.
(OFF pointed down)
5. Wait a sufficient length of time (at least 5 minutes) to allow any gas
which may have accumulated in the burner compartment to escape
6. Turn the gas valve knob clockwise to the ON position.
(ON pointed down)
Step 4