2-13. ELECTRICAL
REQUIREMENTS
(ELECTRIC FRYER)
The electric fryer is available from the factory wired for 208, 220/240,
or 440/480 volts, single or three phase, 60 Hertz service. The proper
power service cable must be ordered as an accessory or provided at
installation. Check the data plate on the inside of the fryer door to
determine the correct power supply.
This fryer
must be adequately and safely grounded (earthed)
or electrical shock could result. Refer to local electrical
codes for correct grounding (earthing) procedures or in
absence of local codes, with The National Electrical Code,
ANSI/NFPA No. 70-(the current edition). In Canada, all
electrical connections are to be made in accordance with CSA
C22.1, Canadian Electrical Code Part 1, and/or local codes.
To avoid electrical shock, this appliance must be equipped
with an external circuit breaker which will disconnect all
ungrounded (unearthed) conductors. The main power switch
on this appliance does
not disconnect all line conductors.
The field supply wiring to the fryer should be of the size indicated in the
data table. It should be an insulated copper conductor rated for 600
volts and 90°C. For runs longer than 50 feet (15.24 m), use the next
larger size wire.
Permanently connected electric fryers with casters must be installed
with flexible conduit and a cable restraint, when installed in the
United States. See illustration at left. Holes are available in the
rear fryer frame for securing the cable restraint to the fryer. The
cable restraint does not prevent the fryer from tipping.
Data Table
Supply Wiring and Fusing for Electric Fryer
Supply Min.
Wire Fuse
Volts Phase KW Amps Size Size
208 Single 11.25 54 6 90
208 Single 13.50 65 4 100
208 Three 11.25 31 10 50
208 Three 13.50 38 8 60
240 Single 11.25 47 6 80
240 Single 13.50 56 6 90
240 Three 11.25 27 10 45
240 Three 13.50 33 8 50
480 Three 11.25 14 14 25
480 Three 13.50 16 14 25
1207 2-11
DRYWALL CONSTRUCTION
Secure I-bolt to a building stud. Do
not attach to drywall only. Preferred
installation is approximately six
inches to either side of service.
Cable restraint must be at least six
inches shorter than flexible conduit.