Blodgett DFG-200 Convection Oven User Manual


 
Installation
12
Gas Connection
PRESSURE REGULATION AND TESTING
DFG-100-3 ovens are rated a t 55,000 BTU/Hr.
(16.2 kW) (58 MJ) per section. DFG-200-L ovens
are rated at 60,000 BTU/Hr. (17.6 kW) (63 MJ) per
section. Each oven has been adjusted atthefacto-
ry to operate with the type of gas specified on the
rating plate.
Inlet Pressure
Natural Propane
Min Max Min Max
W.C. 7.0 10.5 11.0 13.0
kPa 1.742 2.61 2.74 3.23
Manifold Pressure
Natural Propane
W.C. 3.5 10.0
kPa .87 2.49
D
Inlet Pressure --- the pressure of the gas before
it reaches the oven.
D
Manifold Pressure --- the pressure of the gas
as it enters the main burner(s).
D
Min --- the minimum pressure recommended to
operate the ove n.
D
Max --- the maximum pressure at which the
manufacturer warrants the oven’s operation.
Each oven is supplied with a regulator to maintain
the proper gas pressure. The regulator is essen-
tial to the proper operation of the oven and
should not be removed. It is preset to provide the
oven with 3. 5” W.C. (0.87 k Pa) for natural gas and
10.0” W.C. (2.50 kPa) for Propane at the manifold.
DO NOT INSTALL AN ADDITIONAL REGULATOR
WHERE THE OVEN CONNECTS TO THE GAS
SUPPLY UNLESS THE INLET PRESSURE IS
ABOVE MAXIMUM.
Prior to connecting t he oven, gas lines should be
thoroughly purged of all metal filings, shavings,
pipe dope, and other debris. After connection, the
oven should be checked for correct gas pressure.
The oven and its individual shutoff valve must be
disconnected from the gas supply piping s ystem
during any pressure testing of that system at test
pressures in excess of 1/2 psig (13.85” W.C., 3.45
kPa).
The oven must be isolated from the gas supply
piping system by closing its individual manual
shutoff valve during any pressure testing of the
gas piping system a t test pressures equal or less
than 1/2 psig (13.85” W.C., 3.45 kPa).
Gas Connection 2.5” (64 mm)
Gas Connection 3.75” (85.7 mm)
Figure 10