3-19
T -309
Table 3-6 Controller Alarm Indications (Sheet 3 of 4)
AL56
Primary Return
Te mperature Sensor
Failure (RTS)
Alarm 56 is activated by an invalid primary return temperature sensor reading
that is outside the range of --50 to +70_C(--58_F to +158_F). If Alarm 56 is acti-
vated and the primary return is the control sensor, the secondary return sensor
will be used for control if the unit is so equipped. If the unit is not equipped with
a secondary return temperature sensor or it fails, the primary supply sensor will
be used for control.
NOTE
The P5 Pre-Trip test must be run to inactivate the alarm.
AL57
Ambient Tempera-
ture Sensor Failure
Alarm 57 i s triggered by an ambient temperature reading outside the valid range
from --50_C(--58_F) to +70_C (+158_F).
AL58
Compressor High
Pressure Safety
Alarm 58 is triggered when t he compressor high discharge pressure safety switch
remains open for at least one minute. This alarm will remain active until the pres-
sure switch resets, at which time the compressor will restart.
AL59
Heat Termination
Thermostat
Alarm 59 is triggered by the opening of the heat termination thermostat and will
result in the disabling of the heater. This alarm will remain active until the ther-
mostat resets.
AL60
Defrost Temperature
Sensor F ailure
Alarm 60 is an indication of a probable failure of the defrost temperature sensor
(DTS). It is triggered by the opening of the heat termination thermostat (HTT) or
the failure of the DTS to go above set point within two hours of defrost initia-
tion. After one-half hour with a frozen range set point, or one-half hour of contin-
uous compressor run time, if the return air falls below 7_C(45_F), the Controller
checks to ensure t he DTS reading has dropped to 10_C or below. If not, a DTS
failure alarm is given and the defrost mode is operated using the return t empera-
ture sensor. The defrost mode will be terminated after one hour by the Controller.
AL61 Heaters Failure
Alarm 61 i s triggered by detection of improper amperage resulting from heater
activation or deactivation. Each phase of the power source is checked for proper
amperage.This alarm is a display alarm with no resulting failure action, and will
be reset by a proper amp draw of the heater.
AL62
Compressor Circuit
Failure
Alarm 62 is triggered by improper current draw increase (or decrease) resulting
from compressor turn on (or off). The compressor is expected to draw a mini-
mum of 2 amps; failure to do so will activate the alarm. This is a display alarm
with no associated failure action and will be reset by a proper amp draw of the
compressor.
AL63 Current Over Limit
Alarm 63 is triggered by the current limiting system. If the compressor is ON
and current limiting procedures cannot maintain a current level below the user
selected limit, the current limit alarm is activated. This alarm is a display alarm
and is inactivated by power cycling the unit, changing the current limit via the
code select Cd32, or if the current decreases below the activation level.
AL64
Discharge Tempera-
ture Over Limit
Alarm 64 is triggered if the discharge temperature sensed is outside the range of
-- 6 0 _C(--76_F) to 175_C (347_F), or if the sensor is out of range. This is a dis-
play alarm and has no associated failure action.
AL65
Discharge Pressure
Transducer Failure
Alarm 65 is triggered if a compressor discharge transducer is out of range. This is
a display alarm and has no associated failure action.
AL66
Suction Pressure
Transducer Failure
Alarm 66 is triggered if a suction pressure transducer is out of range. This is a
display alarm and has no associated failure action.
AL67
Humidity Sensor
Failure
Alarm 67 is triggered by a humidity sensor reading outside the valid range of 0%
to 100% relative humidity. If alarm AL67 is triggered when the dehumidification
mode is activated, then the dehumidification mode will be deactivated.
AL69
Suction Temperature
Sensor F ailure
Alarm 69 is triggered by a suction t emperature sensor reading outside the valid
range of --60_ C(--76_F) to 150_C (302_F). This is a display alarm and has no
associated failure action.