normal operating temperature. A LOW OIL TEMPERATURE alert will show on the default LID
screen if the operator has the controls set to start.
Software Version
The software version will always be labeled on the PSIO module, and on the back side of the
LID module. On both the Controller ID and LID ID display screens, the software version number
will also appear.
Set Up Machine Control Configuration
As configuration of the 19XL unit is performed, write down all configuration settings. A log,
such as the one shown on pages CL-1 to CL-2, provides a convenient list for configuration
values.
Do not operate the machine before the control configurations have been checked
and a Control Test has been satisfactorily completed. Protection by safety con-
trols cannot be assumed until all control configurations have been confirmed.
WARNING
!
WARNING