reduced at start-up, the starting torque is reduced as well. The object is to reduce the starting
voltage to just the voltage necessary to develop the torque required to get the motor moving.
The voltage and current are then ramped up in a desired period of time. The voltage is reduced
through the use of silicon controlled rectifiers (SCR). Once full voltage is reached, a bypass
contactor is energized to bypass the SCRs.
There are a number of LEDs (light-emitting diodes) that are useful in troubleshooting and
starter checkout on Benshaw, Inc. solid-state starters. These are used to indicate:
voltage to the SCRs
SCR control voltage
power indication
proper phasing for rotation
start circuit energized
overtemperature
ground fault
When voltage is supplied to the solid-state circuitry, the heat sinks within the
starter are at line voltage. Do not touch the heat sinks while voltage is present or
serious injury will result.
WARNING
!
WARNING