System Ready (SYST RDY)
— This light-emitting diode (LED) provides a visual indication
that the EPR is functioning.
Trip Time Potentiometer
— The Trip Time potentiometer has 50 selectable overload trip
classes ranging from 1 to 50 seconds.
Reset Time Potentiometer
— The Reset Time potentiometer has 5 to 120 minutes of motor
cooling reset.
Full Load Amperes (FLA)
— The FLA potentiometer is adjustable from 1 to 1,500 amps,
based on overload frame size.
Trip LED
— The Trip LED provides a visual indication that the EPR has detected an overload
condition and tripped.
Fault (FLT) LED
— The FLT LED is an indicator light.
Reset Button
— The RESET button allows for the manual reset of the EPR.
Trip, Common (COM), and FLA Test Terminals
— The Trip, COM, and FLA test terminals
provide for Digital Voltmeter (DVM) calibration.
Terminal 1 (TB1)
— Terminal 1 is the 120 vac connection to power the EPR.
Terminal 4 (TB4)
— Terminal 4 is the normally closed, electronically isolated EPR contact for
overload trip.
Note: When the System Ready (SYST RDY) LED is a steady green light, no fault has been
found in the solid-state starter operation. When the SYST RDY LED is a steady green