Example 3 — Status03 Display Screen
To access this display from the LID default screen:
1. Press MENU.
2. Press STATUS.
3. Scroll down to highlight STATUS03.
4. Press SELECT.
Note: All values shall be variables available for read operation to a CCN network. Descriptions shown with (*)
support write operations for BEST programming language, data-transfer, and overriding.
Table 2, Example 3 — Status03 Display Screen
Description Range Units
Reference Point Name
(Alarm History)
OPTIONS BOARD 1
*Demand Limit 4-20 mA
*Temp Reset 4-20 mA
*Common CHWS Sensor
*Common CHWR Sensor
*Remote Reset Sensor
*Temp Sensor — Spare 1
*Temp Sensor — Spare 2
*Temp Sensor — Spare 3
OPTIONS BOARD 2
*4-20 mA — Spare 1
*4-20 mA — Spare 2
*Temp Sensor — Spare 4
*Temp Sensor — Spare 5
*Temp Sensor — Spare 6
*Temp Sensor — Spare 7
*Temp Sensor — Spare 8
*Temp Sensor — Spare 9
4-20
4-20
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
4-20
4-20
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
mA
mA
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
mA
mA
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEM
OPT
RES
OPT
CHWS
CHWR
R
RESET
SPARE1
SPARE2
SPARE3
SPARE1
M
SPARE2
M
SPARE4
SPARE5
SPARE6
SPARE7
SPARE8
SPARE9