Carrier PC211 Refrigerator User Manual


 
Example 8 — Service2 Display Screen
To access this display from the LID default screen:
1. Press MENU.
2. Press SERVICE.
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT.
5. Scroll down to highlight SERVICE2.
6. Press SELECT.
Table 2, Example 8 — Service2 Display Screen
Description
Configurable
Range
Units
Reference
Point
Name
Default
Value
OPTIONS BOARD 1
20 mA POWER CONFIGURA-
TION External = 0, Internal = 1
RESET 20 mA Power Source
DEMAND 20 mA Power Source
SPARE ALERT ENABLE
Disable = 0, Low = 1, High = 2
Temp = Alert Threshold
CHWS Temp Enable
CHWS Temp Alert
CHWR Temp Enable
CHWR Temp Alert
Reset Temp Enable
Reset Temp Alert
Spare Temp 1 Enable
Spare Temp 1 Alert
Spare Temp 2 Enable
Spare Temp 2 Alert
Spare Temp 3 Enable
Spare Temp 3 Alert
DISABLE/ENABLE
DISABLE/ENABLE
0-2
–40-245 (–40-118)
0-2
–40-245 (–40-118)
0-2
–40-245 (–40-118)
0-2
–40-245 (–40-118)
0-2
–40-245 (–40-118)
0-2
–40-245 (–40-118)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
res
20 ma
dem
20 ma
chws
en
chws
al
chwr
en
chwr
al
rres
en
rres
al
spr1
en
spr1
al
spr2
en
spr2
al
spr3
en
spr3
al
DISABLE
DISABLE
0
245 (118)
0
245 (118)
0
245 (118)
0
245 (118)
0
245 (118)
0
245 (118)