Carrier PC211 Refrigerator User Manual


 
midnight to 3:00 a.m. weekend cool-down schedule.
Note: This schedule is for illustration only, and is not intended to be a recommended schedule
for chiller operation.
PSIO Software Version 08 and Lower
Whenever the chiller is in the LOCAL mode, the machine will start when the Occupancy
Schedule 01 indicates OCCUPIED. When in the CCN mode, Occupancy Schedule 02 is used.
PSIO Software Version 09 and Higher
The Local Time Schedule is still the Occupancy Schedule 01. The Ice Build Time Schedule is
Schedule 02 and the CCN Default Time Schedule is Schedule 03. The CCN schedule number
is defined on the Config table in the Equipment Configuration table. The schedule number can
change to any value from 03 to 99. If this schedule number is changed on the Config table, the
operator must use the Attach to Network Device table to upload the new number into the
Schedule screen. See Figure 17.