To View and Change Set Points (
Figure 19
)
1.
To view the Set Point table, at the Menu screen press SETPOINT.
2.
There are 4 set points on this screen: Base Demand Limit; LCW Set Point (leaving chilled
water set point); ECW Set Point (entering chilled water set point); and ICE BUILD set point
(PSIO Software Version 09 and higher only). Only one of the chilled water set points can be
active at one time, and the type of set point is activated in the Service menu. ICE BUILD is
also activated and configured in the Service menu.
3.
Press NEXT or PREVIOUS to highlight the desired set point entry.
STATUS SCHEDULE SETPOINT SERVICE
NEXT PREVIOUS SELECT EXIT