CCW — Counterclockwise
CW — Clockwise
Table 6 — Potentiometer Adjustment
Dial
Adjustment Range
Function Factory Setting
Minimum
(CCW)
Maximum
(CW)
Starting Current
100% 400% Sets initial starting current
level.
100%
Ramp Time (Adjust-
able Current Ramp)
2 seconds 30 seconds Sets time during which cur-
rent ramps from the initial
starting level to the maxi-
mum possible current limit
setting.
15 seconds
Current Limit
100% 400% Sets maximum starting cur-
rent.
250%
Pulse Start
0 (Off) 2 seconds Sets duration of 400% cur-
rent pulse. Pulse is used to
break load free.
OFF
Current Trip
50% 400% Sets running current trip. 175%
Power Saver
— — — OFF