Carrier PC211 Refrigerator User Manual


 
Config Table Modifications
Change the values in this table per job data. See certified drawings for values. Modifications
include:
chilled water reset
entering chilled water control (Enable/Disable)
4-20 mA demand limit
auto restart option (Enable/Disable)
remote contact option (Enable/Disable)
Owner-Modified CCN Tables
The following tables are described for reference only.
Occdef Table Modifications
— The Occdef tables contain the Local and CCN time
schedules, which can be modified here, or in the Schedule screen as described previously.
Holidef Table Modifications
—The Holidef tables configure the days of the year that holidays
are in effect. See the holiday paragraphs in the Controls section for more details.
Brodefs Table Modifications
— The Brodefs screen defines the outside-air temperature
sensor and humidity sensor if one is to be installed. It will define the start and end of daylight
savings time. Enter the dates for the start and end of daylight savings if required for the location.
Brodefs also will activate the Broadcast function which enables the holiday periods that are
defined on the LID.
Other Tables
—The Alarmdef, Cons-def, and Runt-def contain tables for use with a CCN