Carrier PC211 Refrigerator User Manual


 
Operation Features:
2 chiller lead/lag
addition of a third chiller for backup
manual rotation of lead chiller
load balancing if configured
staggered restart of the chillers after a power failure
chillers may be piped in parallel or in series chilled water flow
Common Point Sensor Installation
Lead/lag operation does not require a common chilled water point sensor. Common point
sensors can be added to the 8-input option module, if desired. Refer to the certified drawings for
termination of sensor leads.
Note:
If the common point sensor option is chosen on a chilled water system, both machines
should have their own 8-input option module and common point sensor installed. Each
machine will use its own common point sensor for control, when that machine is desig-
nated as the lead chiller. The PIC cannot read the value of common point sensors
installed on other machines in the chilled water system.
When installing chillers in series, a common point sensor should be used. If a common point
sensor is not used, the leaving chilled water sensor of the upstream chiller must be moved into
the leaving chilled water pipe of the downstream chiller.
If return chilled water control is required on chillers piped in series, the common point return