Control and Oil Heater Voltage Selector (S1)
It is possible to use either 115 v or 230 v incoming control power in the power panel. The
switch is set to the voltage used at the job site.
LID Operation and Menus (
Figure 13
,
Figure 14
,
Figure 15
,
Figure 16
,
Figure
17
,
Figure 18
, and
Figure 19
)
General
The LID display will automatically revert to the default screen after 15 minutes if no
softkey activity takes place and if the machine is not in the Pumpdown mode (Figure
13).
When not in the default screen, the upper right-hand corner of the LID always dis-
plays the name of the screen that you have entered (Figure 14).
The LID may be configured in English or SI units, through the LID configuration
screen.
Local Operation — By pressing the LOCAL softkey, the PIC is now in the LOCAL
operation mode and the control will accept modification to programming from the LID
only. The PIC will use the Local Time Schedule to determine machine start and stop
times.
CCN Operation — By pressing the CCN softkey, the PIC is now in the CCN operation