19XL PIC CONFIG TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
RESET TYPE 1
Degrees Reset at 20 mA
–30 to 30
(–17 to 17)
DEG F
(DEG C)
10
(6)
RESET TYPE 2
Remote Temp (No Reset)
–40 to 245
(–40 to 118)
DEG F
(DEC C)
85
(29)
Remote Temp (Full Reset)
–40 to 245
(–40 to 118)
DEG F
(DEG C)
65
(18)
Degrees Reset
–30 to 30
(–17 to 17)
DEG F
(DEG C)
10
(6)
RESET TYPE 3
CHW Temp (No Reset)
0to15
(0 to 8)
DEG F
(DEG C)
10
(6)
CHW Temp (Full Reset)
0to15
(0 to 8)
DEG F
(DEG C)
0
(0)
Degrees Reset
–30 to 30
(–17 to 17)
DEG F
(DEG C)
5
(3)
Select/Enable Reset Type 0to3 0
ECW Control Option Disable/Enable Disable
Demand Limit at 20 mA 40 to 100 % 40
20 mA Demand Limit Option Disable/Enable Disable
Auto Restart Option Disable/Enable Disable
Remote Contacts Option Disable/Enable Disable
Temp Pulldown Deg/Min 2to10 3
Load Pulldown %/Min 5to20 10
Select Ramp Type:
Temp=0/Load=1
0/1 1
Loadshed Group Number 0to99 0
Loadshed Demand Delta 0to60 % 20
Maximum Loadshed Time 0 to 120 Min 60
CCN Occupancy Config:
Schedule Number
3to99 3
CCN Occupancy Config:
Broadcast Option
Disable/Enable Disable
ICE BUILD Option Disable/Enable Disable
ICE BUILD TERMINATION:
0 =Temp, 1 =Contacts, 2 =Both
0, 1, 2 0
ICE BUILD RECYCLE Option Disable/Enable Disable
CL-5