Example 7 — Service1 Display Screen
To access this display from the LID default screen:
1. Press MENU.
2. Press SERVICE.
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT.
5. Scroll down to highlight SERVICE1.
6. Press SELECT.
Table 2, Example 7 — Service1 Display Screen
Description
Configurable
Range
Units
Reference
Point
Name
Default Value
Motor Temp Override
Cond Press Override
Refrig Override Delta T
Chilled Medium
Brine Refrig Trippoint
Compr Discharge Alert
Bearing Temp Alert
Water Flow Verify Time
Oil Press Verify Time
Water/Brine Deadband
Recycle Restart Delta T
Surge Limit/HGBP Option
Select: Surge=0, HGBP=1
Surge/HGBP Delta T1
Surge/HGBP Delta P1
Min. Load Points (T1/P1)
Surge/HGBP Delta T2
150-200 (66-93)
150-245 (1034-1689)
[90-200 (620-1379)]
2-5 (1-3)
Water/Brine
8-40 (–13.3-4)
125-200 (52-93)
175-185 (79-85)
0.5-5
15-300
0.5-2.0 (0.3-1.1)
2.0-10.0 (1.1-5.6)
0/1
0.5-15 (0.3-8.3)
50-170 (345-1172)
[30-170 (207-1172)]
0.5-15 (0.3-8.3)
50-170 (345-1172)
DEG F (DEG C)
PSI (kPa)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
MIN
SEC
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
PSI (kPA)
DEG F (DEG C)
mt
over
cp
over
ref
over
medium
br
trip
cd
alert
tb
alert
wflow
t
oilpr
t
cw
db
rcyc
dt
srg
hgbp
hgb
dt1
hgb
dp1
hgb
dt2
200 (93)
195 (1345) [125 (862)]
3
(1.6
)
WATER
33 (1)
200 (93)
175 (79)
5
15
1.0 (0.6)
5 (2.8)
0
1.5 (0.8)
75 (517) [50 (345)]
10 (5.6)