Example 2 — Status02 Display Screen
To access this display from the LID default screen:
1. Press MENU.
2. Press STATUS.
3. Scroll down to highlight STATUS02.
4. Press SELECT.
Note: All values are variables available for read operation to a CCN. Descriptions shown with (*) support
write operations from the LID only.
Table 2, Example 2 — Status02 Display Screen
Description
Point Type
Units
Reference Point
Name (Alarm
History)
Input Output
Hot Gas Bypass Relay
*Chilled Water Pump
Chilled Water Flow
*Condenser Water Pump
Condenser Water Flow
Compressor Start Relay
Compressor Start Contact
Compressor Run Contact
Starter Fault Contact
Pressure Trip Contact
Single Cycle Dropout
Oil Pump Relay
Oil Heater Relay
Motor Cooling Relay
*Tower Fan Relay
Compr. Shunt Trip Relay
Alarm Relay
Spare Prot Limit Input
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
OFF/ON
OFF/ON
NO/YES
OFF/ON
NO/YES
OFF/ON
OPEN/CLOSED
OPEN/CLOSED
OPEN/CLOSED
OPEN/CLOSED
NORMAL/ALARM
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
NORMAL/ALARM
ALARM/NORMAL
HGBR
CHWP
EVFL
CDP
CDFL
CMPR
1CR
AUX
RUN
AUX
STR
FLT
PRS
TRIP
V1
CYCLE
OILR
OILH
MTRC
TFR
TRIPR
ALM
SPR
PL