Carrier PC211 Refrigerator User Manual


 
Legend For Table 10, A - N
1CR AUX Compressor Start Contact OILPD Oil Pressure
CA P Compressor Current OILT Oil Sump Temperature
CDFL Condenser Water Flow PIC Product Integrated Control
CHIL S S Chiller Start/Stop PRS TRIP Pressure Trip Contact
CMPD Discharge Temperature PSIO Processor Sensor Input/Output Module
CRP Condenser Pressure RLA Rated Load Amps
ERT Evaporator Refrigerant Temperature RUN AUX Compressor Run Contact
EVFL Chilled Water Flow SPR PL Spare Protective Limit Input
GV TRG Target Guide Vane Position SMM Starter Management Module
LID Local Interface Device STR FLT Starter Fault
MTRB Bearing Temperature TXV Thermostatic Expansion Valve
MTRW Motor Winding Temperature V P Line Voltage: Percent
V REF Voltage Reference
Table 10A — Shutdown with On/Off/Reset-Off
Primary Message Secondary Message Probable Cause/Remedy
Manually Stopped —
Press
CCN or Local to Start PIC in OFF mode, press the CCN or
local softkey to start unit.
Terminate Pumpdown
Mode
To Select CCN or Local Enter the Control Test table and
select Terminate Lockout to unlock
compressor.
Shutdown In Progress
Compressor Unloading Machine unloading before shutdown
due to Soft Stop feature.
Shutdown In Progress
Compressor Deenergized Machine compressor is being com-
manded to stop. Water pumps are
deenergized within one minute.
Ice Build
Operation Complete Machine shutdown from Ice Build
operation.