Carrier PC211 Refrigerator User Manual


 
19XL PIC SERVICE2 TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
RESET 20 mA Power Source 0/1 0 =EXTERNAL, 1 =INTERNAL 0
DEMAND 20 mA Power Source 0/1 0 =EXTERNAL, 1 =INTERNAL 0
CHWS Temp Enable 0 to 2 0 =DISABLE, 1 =HIGH, 2 =LOW 0
CHWS Temp Alert
–40 to 245
(–40 to 118)
DEG F
(DEG C)
245
(118)
CHWR Temp Enable 0 to 2 0 =DISABLE, 1 =HIGH, 2 =LOW 0
CHWR Temp Alert
–40 to 245
(–40 to 118)
DEG F
(DEG C)
245
(118)
Reset Temp Enable 0 to 2 0 =DISABLE, 1 =HIGH, 2 =LOW 0
Reset Temp Alert
–40 to 245
(–40 to 118)
DEG F
(DEG C)
245
(118)
Spare Temp 1 Enable 0 to 2 0 =DISABLE, 1 =HIGH, 2 =LOW 0
Spare Temp 1 Alert
–40 to 245
(–40 to 118)
DEG F
(DEG C)
245
(118)
Spare Temp 2 Enable 0 to 2 0 =DISABLE, 1 =HIGH, 2 =LOW 0
Spare Temp 2 Alert
–40 to 245
(–40 to 118)
DEG F
(DEG C)
245
(118)
Spare Temp 3 Enable 0 to 2 0 =DISABLE, 1 =HIGH, 2 =LOW 0
Spare Temp 3 Alert
–40 to 245
(–40 to 118)
DEG F
(DEG C)
245
(118)
SPARE 1 20 mA Power Source 0/1 0 =EXTERNAL, 1 =INTERNAL 0
SPARE 2 20 mA Power Source 0/1 0 =EXTERNAL, 1 =INTERNAL 0
Spare Temp 4 Enable 0 to 2 0 =DISABLE, 1 =HIGH, 2 =LOW 0
Spare Temp 4 Alert
–40 to 245
(–40 to 118)
DEG F
(DEG C)
245
(118)
Spare Temp 5 Enable 0 to 2 0 =DISABLE, 1 =HIGH, 2 =LOW 0
Spare Temp 5 Alert
–40 to 245
(–40 to 118)
DEG F
(DEG C)
245
(118)
Spare Temp 6 Enable 0 to 2 0 =DISABLE, 1 =HIGH, 2 =LOW 0
Spare Temp 6 Alert
–40 to 245
(–40 to 118)
DEG F
(DEG C)
245
(118)
Spare Temp 7 Enable 0 to 2 0 =DISABLE, 1 =HIGH, 2 =LOW 0
Spare Temp 7 Alert
–40 to 245
(–40 to 118)
DEG F
(DEG C)
245
(118)
Spare Temp 8 Enable 0 to 2 0 =DISABLE, 1 =HIGH, 2 =LOW 0
Spare Temp 8 Alert
–40 to 245
(–40 to 118)
DEG F
(DEG C)
245
(118)
Spare Temp 9 Enable 0 to 2 0 =DISABLE, 1 =HIGH, 2 =LOW 0
Spare Temp 9 Alert
–40 to 245
(–40 to 118)
DEG F
(DEG C)
245
(118)
CL-9