current unbalance
run state
These LEDs are further explained in the Check Starter and Troubleshooting Guide sections.
Unit-Mounted Wye-Delta Starter (Optional)
The 19XL machine may be equipped with a wye-delta starter mounted on the unit. This
starter is intended for use with low-voltage motors (under 600 v). It reduces the starting current
inrush by connecting each phase of the motor windings into a wye configuration. This occurs
during the starting period when the motor is accelerating up to speed. After a time delay, once
the motor is up to speed, the starter automatically connects the phase windings into a delta
configuration.
Click here for Figure 5 — Cutler-Hammer
®
Solid-State Starter, Internal View
Click here for Figure 6 — Benshaw, Inc. Solid-State Starter, Internal View
Click here for Figure 7 — Typical Starter Front View (Solid-State Starter Shown)