Table 6 — Part Load Data Percent Displacement, Standard Units without Minimum Load Valve
NOTE: These capacity steps may vary due to different capacity staging sequences.
30RA UNIT SIZE
CONTROL
STEPS
LOADING SEQ A LOADING SEQ B
% Displacement Compressor % Displacement Compressor
010,015 (60 Hz)
1 100 A1 ——
015 (50 Hz), 018
150A1——
2 100 A1,A2 ——
022 (60 Hz)
142A1——
2 100 A1, A2 ——
022 (50 Hz), 025, 030
150A1 ——
2 100 A1,A2 ——
032, 035 (60 Hz)
1 25A1 40B1
2 60 A1,A2 65 A1,B1
3 100 A1,A2,B1 100 A1,A2,B1
035 (50 Hz)
1 33A1 33B1
2 67 A1, A2 67 A1, B1
3 100 A1, A2, B1 100 A1, A2, B1
040
1 32A1 37B1
2 63 A1, A2 68 A1, B1
3 100 A1, A2, B1 100 A1, A2, B1
042, 045 (50 Hz), 050,
055
1 25A1 25B1
2 50 A1,B1 50 A1,B1
3 75A1,A2,B1 75A1,B1,B2
4 100 A1,A2,B1,B2 100 A1,A2,B1,B2
045 (60 Hz)
1 22A1 22B1
2 44 A1,B1 44 A1,B1
3 72A1,A2,B1 72A1,B1,B2
4 100 A1,A2,B1,B2 100 A1,A2,B1,B2