Table 17 — Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
OPT1
UNIT OPTIONS 1 HARDWARE
FLUD X COOLER FLUID Default: Water
1 = Water
2 = Medium Temperature Brine
MLV.S YES/NO MINIMUM LOAD VALVE SELECT
MMR.S YES/NO MOTORMASTER SELECT
RG.EN ENBL/DSBL RETURN GAS SENSOR ENABLE Default: DISABLED
CPC ON/OFF COOLER PUMP CONTROL Default: On
PM1E YES/NO COOLER PUMP 1 ENABLE
PM2E YES/NO COOLER PUMP 2 ENABLE
PM.P.S YES/NO COOLER PMP PERIODIC STRT Default: No
PM.SL X COOLER PUMP SELECT Default: Automatic
0 = Automatic
1 = Pump 1 Starts first
2 = Pump 2 Starts first
PM.DY XX MIN COOLER PUMP SHUTDOWN DLY 0 to 10 minutes, Default: 1 min.
PM.DT XXXX HRS PUMP CHANGEOVER HOURS Default: 500 hours
ROT.P YES/NO ROTATE COOLER PUMPS NOW User Entry
EMM YES/NO EMM MODULE INSTALLED
OPT2
UNIT OPTIONS 2 CONTROLS
CTRL X CONTROL METHOD Default: Switch
0 = Enable/Off/Remote Switch
2 = Occupancy
3 = SCN Control
SCNA XXX SCN ADDRESS
Default: 1
Range: 1 to 239
SCNB XXX SCN BUS NUMBER
Default: 0
Range: 0 to 239
BAUD X SCN BAUD RATE Default: 9600
1 = 2400
2 = 4800
3 = 9600
4 = 19,200
5 = 38,400
LOAD X LOADING SEQUENCE SELECT Default: Equal
1 = Equal
2 = Staged
LLCS X LEAD/LAG CIRCUIT SELECT Default: Automatic
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
LCWT
XX.X
∆
F
HIGH LCW ALERT LIMIT
Default: 60
Range: 2 to 60
°
F
DELY XX MINUTES OFF TIME
Default: 0 Minutes
Range: 0 to 15 Minutes
ICE.M ENBL/DSBL ICE MODE ENABLE Default: Disable
CLS.C ENBL/DSBL CLOSE CONTROL SELECT Default: Disable
LS.MD X LOW SOUND MODE SELECT Default: 0
0 = Mode Disable
1 = Fan Noise Only
2 = Fan/Compressor Noise
LS.ST 00:00 LOW SOUND START TIME Default: 00:00
LS.ND 00:00 LOW SOUND END TIME Default: 00:00
LS.LT XXX % LOW SOUND CAPACITY LIMIT
Default: 100%
Range: 0 to 100%
RSET
RESET COOL TEMP
CRST X COOLING RESET TYPE Default: No Reset
0 = No Reset
1 = 4 to 20 mA Input
2 = Outdoor Air Temperature
3 = Return Fluid
4 = Space Temperature
MA.DG
XX.X
∆
F
4-20 - DEGREES RESET
Default: 0.0
∆
F
Range: –30 to 30
∆
F
RM.NO
XXX.X
°
F
REMOTE - NO RESET TEMP
Default: 125
F (51.7
C)
Range: 0° to 125
F
ENTER
ENTER