81
RESETCON (Temperature Reset and Demand Limit)
SCHEDOVR (Timed Override Setup)
SETPOINT
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
COOLING RESET
Cooling Reset Type 0 = No Reset
1 = 4-20 mA input
2 = External temp – OAT
3 = Return Fluid
4 = External temp - SPT
0 CRST_TYP
4-20 MA RESET
4-20 – Degrees Reset –30 to 30 0.0
∆
∆∆
∆
F 420_DEG
REMOTE RESET
Remote – No Reset Temp 0 to 125 125.0
°
°°
°
FREM_NO
Remote – Full Reset Temp 0 to 125 0.0
°
°°
°
FREM_FULL
Remote – Degrees Reset –30 to 30 0.0
∆
∆∆
∆
FREM_DEG
RETURN TEMPERATURE RESET
Return – No Reset Temp 0 to 125 10.0
∆
∆∆
∆
FRTN_NO
Return – Full Reset Temp 0 to 125 0.0
∆
∆∆
∆
FRTN_FULL
Return – Degrees Reset –30 to 30 0.0
∆
∆∆
∆
FRTN_DEG
DEMAND LIMIT
Demand Limit Select 0 = None
1 = External switch input
2 = 4-20 mA input
3 = Loadshed
0DMD_CTRL
Demand Limit at 20 mA 0 to 100 100 % DMT20MA
Loadshed Group Number 0 to 99 0 SHED_NUM
Loadshed Demand Delta 0 to 60 0 % SHED_DEL
Maximum Loadshed Time 0 to 120 60 minutes SHED_TIM
Demand Limit Switch 1 0 to 100 80 % DLSWSP1
Demand Limit Switch 2 0 to 100 50 % DLSWSP2
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Schedule Number 0 to 99 1 SCHEDNUM
Override Time Limit 0 to 4 0 hours OTL
Timed Override Hours 0 to 4 0 hours OVR_EXT
Timed Override No/Yes No TIMEOVER
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
COOLING
Cooling Setpoint 1 –20 to 70 44.0
°
°°
°
FCSP1
Cooling Setpoint 2 –20 to 70 44.0
°
°°
°
FCSP2
ICE Setpoint –20 to 32 32.0
°
°°
°
FCSP3
RAMP LOADING
Cooling Ramp Loading 0.2 to 2.0 1.0 CRAMP
Brine Freeze Point –20 to 34 34.0
°
°°
°
F BRN_FRZ