Table 38 — Motormaster® V Program Parameters for Operating Modes
LEGEND
PARAMETERS DESCRIPTION
MODE
1
MODE
2
MODE
3
MODE
4
P01
Line Voltage: 01 = low line, 02 = high line 01 02 01 02
P02
Sterlco Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz 01 01 01 01
P03
Startup mode: flying restart 06 06 06 06
P04
Stop mode: coast to stop 01 01 01 01
P05
Standard Speed source: 01= keypad,
04=4-20mA (NO PI), 05= R22, 06=R134a
05 05 05 05
P06
TB-14 output: 01 = none 01 01 01 01
P08
TB-30 output: 01 = none 01 01 01 01
P09
TB-31 Output: 01 = none 01 01 01 01
P10
TB-13A function sel: 01 = none 01 01 01 01
P11
TB-13B function sel: 01 = none 01 01 01 01
P12
TB-13C function sel: 01 = none 01 01 01 01
P13
TB-15 output: 01 = none 01 01 01 01
P14
Control: 01 = Terminal strip 01 01 01 01
P15
Serial link: 02 = enabled 9600,8,N,2 with timer 02 02 02 02
P16
Units editing: 02 = whole units 02 02 02 02
P17
Rotation: 01 = forward only, 03 = reverse only 01 01 01 01
P19
Acceleration time: 10 sec 10 10 10 10
P20
Deceleration time: 10 sec 10 10 10 10
P21
DC brake time: 0 0 0 0 0
P22
DC BRAKE VOLTAGE 0% 0 0 0 0
P23
Min freq = 8 Hz ~ 100 – 160 rpm 8 8 8 8
P24
Max freq 60 60 50 50
P25
Current limit: (%) 125 110 125 110
P26
Motor overload: 100 100 100 100 100
P27
Base freq: 60 or 50 Hz 60 60 50 50
P28
Fixed boost: 0.5% at low frequencies 0.5 0.5 0.5 0.5
P29
Accel boost: 0% 0 0 0 0
P30
Slip compensation: 0% 0 0 0 0
P31
Preset spd #1: speed if loss of control signal 57 57 47 47
P32
Preset spd #2: 0 0 0 0 0
P33
Preset spd #3: 0 0 0 0 0
P34
Preset spd 4 default — R22 set point.
TB12-2 open
18.0 18.0 18.0 18.0
P35
Preset spd 5 default — R134a set point.
TB12-2 closed
12.6 12.6 12.6 12.6
P36
Preset spd 6 default 0 0 0 0
P37
Preset spd 7 default 0 0 0 0
P38
Skip bandwidth 0 0 0 0
P39
Speed scaling 0 0 0 0
P40
Frequency scaling 50 or 60 Hz 60 60 50 50
P41
Load scaling: default (not used so NA) 200 200 200 200
P42
Accel/decel #2: default (not used so NA) 60 60 60 60
P43
Serial address 1 1 1 1
P44
Password:111 111 111 111 111
P45
Speed at min signal: 8 Hz; used when PID
mode is disabled and 4-20mA input is at 4 mA
8888
P46
Speed at max feedback: 60 or 50 Hz. Used
when PID disabled and 4-20mA input is at 20 mA
60 60 50 50
P47
Clear history? 01 = maintain. (set to 02 to clear) 01 01 01 01
P48
Program selection: Program 1 – 12 01 02 03 04
P61
PI Mode: 05= reverse, 0-5V, 01 = no PID 05 05 05 05
P62
Min feedback = 0 (0V *10) 0 0 0 0
P63
Max feedback = 50 (5V * 10) 50 50 50 50
P64
Proportional gain = 4% 4 4 4 4
P65
Integral gain = .2 .2 .2 .2 .2
P66
PI acell/decel (set point change filter) = 5 5 5 5 5
P67
Min alarm 0 0 0 0
P68
Max alarm 0 0 0 0
NA —
Not Applicable
PID —
Proportional Integral Derivative
TB —
Terminal Block