Sterling 30RA010-055 Refrigerator User Manual


 
33
Table 17 Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
RSET (cont)
RM.F
XXX.X
°
F
REMOTE - FULL RESET TEMP
Default: 0.0
°
F (-17.8
C)
Range: 0
°
to 125
F
RM.DG
XX.X
°
F
REMOTE - DEGREES RESET
Default: 0.0
°
F
Range: 30 to 30
F
RT.NO
XXX.X
F
RETURN - NO RESET TEMP
Default: 10.0
F (5.6
C)
Range: 0
°
to 125
F COOLER
T
RT.F
XXX.X
F
RETURN - FULL RESET TEMP
Default: 0.0
F (0.0
C)
Range: 0
°
to 125
F COOLER
T
RT.DG
XX.X
°
F
RETURN - DEGREES RESET
Default: 0.0
°
F
Range: 30 to 30
F
(34.4 to -1.1 C)
DMDC X DEMAND LIMIT SELECT Default: None
0 = None
1 = Switch
2 = 4 to 20 mA Input
3 = SCN Loadshed
DM20 XXX % DEMAND LIMIT AT 20 MA
Default: 100%
Range: 0 to 100%
SHNM XXX LOADSHED GROUP NUMBER
Default: 0
Range: 0 to 99
SHDL XXX % LOADSHED DEMAND DELTA
Default: 0%
Range: 0 to 60%
SHTM XXX MAXIMUM LOADSHED TIME
Default: 60 minutes
Range: 0 to 120 minutes
DLS1 XXX % DEMAND LIMIT SWITCH 1
Default: 80%
Range: 0 to 100%
DLS2 XXX % DEMAND LIMIT SWITCH 2
Default: 50%
Range: 0 to 100%
LLEN ENBL/DSBL LEAD/LAG CHILLER ENABLE Default: Disable
MSSL SLVE/MAST MASTER/SLAVE SELECT Default: Master
SLVA XXX SLAVE ADDRESS
Default: 2
Range: 0 to 239
LLBL X LEAD/LAG BALANCE SELECT Default: Master Leads
0 = Master Leads
1 = Slave Leads
2 = Automatic
LLBD XXX LEAD/LAG BALANCE DELTA
Default: 168 hours
Range: 40 to 400 hours
LLDY XXX LAG START DELAY
Default: 5 minutes
Range: 0 to 30 minutes
PARA YES PARALLEL CONFIGURATION Default: YES (CANNOT BE CHANGED)
SLCT
SETPOINT AND RAMP LOAD
CLSP X COOLING SETPOINT SELECT Default: Single
0 = Single
1 = Dual Switch
2 = Dual SCN Occupied
3 = 4 to 20 mA Input (requires
EMM)
RL.S ENBL/DSBL RAMP LOAD SELECT Default: Enable
CRMP X.X COOLING RAMP LOADING
Default: 1.0
Range: 0.2 to 2.0
SCHD XX SCHEDULE NUMBER
Default: 1
Range: 1 to 99
Z.GN X.X DEADBAND MULTIPLIER
Default: 2.0
Range: 1.0 to 4.0
SERV
SERVICE CONFIGURATION
EN.A1 ENBL/DSBL ENABLE COMPRESSOR A1 Unit dependent
EN.A2 ENBL/DSBL ENABLE COMPRESSOR A2 Unit dependent
EN.B1 ENBL/DSBL ENABLE COMPRESSOR B1 Unit dependent
EN.B2 ENBL/DSBL ENABLE COMPRESSOR B2 Unit dependent
BCST
BROADCAST CONFIGURATION
T.D.BC ON/OFF SCN TIME/DATE BROADCAST
OAT.B ON/OFF SCN OAT BROADCAST
G.S.BC ON/OFF GLOBAL SCHEDULE BROADCAST
BC.AK ON/OFF SCN BROADCAST ACKER
ENTER