Sterling 30RA010-055 Refrigerator User Manual


 
19
Table 7 Part Load Data Percent Displacement, Standard Units with Minimum Load Valve
*Minimum Load Valve energized.
NOTE: These capacity steps may vary due to different capacity
staging sequences.
30RA UNIT SIZE
CONTROL
STEPS
LOADING SEQ A LOADING SEQ B
% Displacement Compressor % Displacement Compressor
010 (50/60 Hz)
1
2
69/ 71
100/100
A1*
A1
015 (60 Hz)
1
2
79
100
A1*
A1
015 (50 Hz)
1
2
3
28
50
100
A1*
A1
A1,A2
018 (50/60 Hz)
1
2
3
32/ 31
50/ 50
100/100
A1*
A1
A1,A2
022 (50/60 Hz)
1
2
3
27/ 35
42/ 50
100/100
A1*
A1
A1,A2
025 (50/60 Hz)
1
2
3
38/ 37
50/ 50
100/100
A1*
A1
A1,A2
030
1
2
3
39
50
100
A1*
A1
A1,A2
032
1
2
3
4
15
25
60
100
A1*
A1
A1,A2
A1,A2,B1
30
40
65
100
B1*
B1
A1,B1
A1,A2,B1
035 (50/60 Hz)
1
2
3
4
16/25
25/33
60/67
100
A1*
A1
A1,A2
A1,A2,B1
32/25
40/33
65/67
100
B1*
B1
A1,B1
A1,A2,B1
040
1
2
3
4
24
32
63
100
A1*
A1
A1,A2
A1,A2,B1
29
37
68
100
B1*
B1
A1,B1
A1,A2,B1
042
1
2
3
4
5
18
25
50
75
100
A1*
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
18
25
50
75
100
B1*
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
045 (60 Hz)
1
2
3
4
5
15
22
44
72
100
A1*
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
15
22
44
72
100
B1*
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
045 (50 Hz), 050
1
2
3
4
5
19
25
50
77
100
A1*
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
19
25
50
77
100
B1*
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
055
1
2
3
4
5
20
25
50
75
100
A1*
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
20
25
50
75
100
B1*
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2