Sterling 30RA010-055 Refrigerator User Manual


 
30
Table 13 Pressure Mode and Sub-Mode Directory
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 14 Set Point and Sub-Mode Directory
Table 15 Inputs Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
PRC.A PRESSURES CIRCUIT A
DP.A XXX.X PSIG DISCHARGE PRESSURE
SP.A XXX.X PSIG SUCTION PRESSURE
PRC.B PRESSURES CIRCUIT B See Note
DP.B XXX.X PSIG DISCHARGE PRESSURE See Note
SP.B XXX.X PSIG SUCTION PRESSURE See Note
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
COOL COOLING SETPOINTS
CSP.1
XXX.X
°
F
COOLING SETPOINT 1 Default: 44 F
CSP.2
XXX.X
°
F
COOLING SETPOINT 2 Default: 44 F
CSP.3
XXX.X
°
F
ICE SETPOINT Default: 32 F
HEAD HEAD PRESSURE SETPOINTS
HD.P.A
XXX.X
°
F
CALCULATED HP SETPOINT A
Default: 113 F
(Read Only)
HD.P.B
XXX.X
°
F
CALCULATED HP SETPOINT B
Default: 113 F
(Read Only)
FRZ BRINE FREEZE SETPOINT
BR.FZ
XXX.X
°
F
BRINE FREEZE POINT Default: 34 F
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
GEN.I GENERAL INPUTS
STST STRT/STOP START/STOP SWITCH
FLOW ON/OFF COOLER FLOW SWITCH
PM.F.1 OPEN/CLSE COOLER PUMP 1 INTERLOCK
LD.PM X Lead Pump
1 = Pump 1
2 = Pump 2
3 = No Pump
PM.F.2 OPEN/CLSE COOLER PUMP 2 INTERLOCK
HT.RQ ON/OFF HEAT REQUEST
DLS1 ON/OFF DEMAND LIMIT SWITCH 1
DLS2 ON/OFF DEMAND LIMIT SWITCH 2
ICED ON/OFF ICE DONE
DUAL ON/OFF DUAL SETPOINT SWITCH
CRCT CIRCUITS INPUTS
FKA1 ON/OFF COMPRESSOR A1 FEEDBACK
FKA2 ON/OFF COMPRESSOR A2 FEEDBACK
FKB1 ON/OFF COMPRESSOR B1 FEEDBACK See Note
FKB2 ON/OFF COMPRESSOR B2 FEEDBACK See Note
4-20 4-20 MA INPUTS
DMND XX.X MA 4-20 MA DEMAND SIGNAL
RSET XX.X MA 4-20 MA RESET SIGNAL
CSP XX.X MA 4-20 MA COOLING SETPOINT
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER